58 Program features
Combined
The combined is suitable for applications where you need to maintain tension from
zero speed to maximum speed
Combined method is a combination of direct and proportional mode. Here, the trim for
zero speed is defined by
and the trim for speed greater than zero
. The trim value is directly proportional to
.
The process speed reference is connected in
. For
example, if EXT1 control mode is used and the reference source is AI scaled, then
should be configured to
AI1 scaled.
The
is calculated using below formula:
The below graph shows the trim increase in combined mode.
Note:
In the above graph, it is assumed that the PID output is limited/stable at 100.
This is for understanding purpose only. In real case scenario, PID output can vary
based on the setpoint and actual.
Example
If,
=
= 1500 rpm
=
= 1500
Par40.05
Par30.12 Par40.54
1 Par40.54
–
Par40.53
+
Par40.55
=
ct
0