Parameters 217
Enable
Force auto restart enabled. Parameter
is ignored. The drive never trips on the undervoltage fault and
the start signal is on forever. When he DC voltage is restored,
the normal operation continues.
1
22
Speed reference selection; motor potentiometer settings.
See the control chain diagrams on pages
…
.
Displays the output of the speed reference selection block.
See the control chain diagram on page
This parameter is read-only.
-
-30000.00…
30000.00 rpm
Value of the selected speed reference.
See par.
Selects Ext1 speed reference source 1.
Two signal sources can be defined by this parameter and
. A mathematical function (
) applied to the two signals creates an Ext1
reference (A in the figure below).
A digital source selected by
can be
used to switch between Ext1 reference and the
corresponding Ext2 reference defined by parameters
(B in the figure below).
Zero
None.
0
No.
Name/Value
Description
Def/FbEq16
1
0
MUL
SUB
ADD
MIN
MAX
0
AI
FB
…
…
0
AI
FB
…
…
MUL
SUB
ADD
MIN
MAX
0
AI
FB
…
…
0
AI
FB
…
…
A
B
Ext1
Ext2
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...