428 Fault tracing
5690
PU communication
internal
Internal communication error.
Contact your local ABB representative.
5691
Measurement circuit
ADC
Measurement circuit fault.
Contact your local ABB representative.
5692
PU board powerfail
Power unit power supply
failure.
Contact your local ABB representative.
5693
Measurement circuit
DFF
Measurement circuit fault.
Contact your local ABB representative.
5695
Reduced run
Configured power units not
found.
Configure the power units.
5697
Charging feedback
Charging feedback signal
missing.
Check the feedback signal coming from
the charging system
5698
Unknown PU fault
The power unit logic generated
a fault which is not known by
software.
Check the logic and software
compatibility.
50A0
Fan
Cooling fan stuck or
disconnected.
Check fan operation and connection.
Replace fan if faulty.
6181
FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6306
FBA A mapping file
Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6481
Task overload
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6487
Stack overflow
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A3
Application loading
Application file incompatible or
corrupted.
Check the auxiliary code. See actions for
each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
8007 The application contains the
wrong system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
8008 The application is empty.
In Automation Builder, give a “Clean”
command and reload the application.
8009 The application contains
invalid tasks.
In Automation Builder, check application
task configuration, give a “Clean all”
command, and reload the application.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...