Parameters 357
Clear all
Restores all editable parameter values to default values,
except
• end user texts, such as customized warnings and faults,
and the drive name
• control macro selection and the parameter defaults
implemented by it
• parameter
and the differentiated
defaults implemented by it
• group
parameters.
62
Reset home view
Restores the home view layout back to show the values of the
default parameters defined by the control macro in use
512
Reset end user
texts
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning texts
and currency unit.
Note:
PID unit is reset only if it is user editable text, that is,
parameter
is set to User text.
1024
All to factory
defaults
Restores all drive parameters and settings back to initial
factory values, except
• parameter 95.20 HW options word 1 and the differentiated
defaults implemented by it.
34560
Saves the valid parameter values to the permanent memory
on the drive control unit to ensure that operation can continue
after cycling the power. Save the parameters with this
parameter
• to store values sent from the fieldbus
• when using ex24 V DC power supply to the control
unit: to save parameter changes before you power down
the control unit. The supply has a very short hold-up time
when powered off.
Note:
A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Save completed.
0
Save
Save in progress.
1
Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
No action
1 = No action.
0
Reboot
1 = Reboot the control unit.
1
Shows the status of the user parameter sets.
This parameter is read-only.
See also section
(page
).
n/a
No user parameter sets have been saved.
0
Loading
A user set is being loaded.
1
Saving
A user set is being saved.
2
Faulted
Invalid or empty parameter set.
3
User1 IO active
User set 1 has been selected by parameters
and
4
User2 IO active
User set 2 has been selected by parameters
and
5
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...