Parameters 323
Data storage parameter 12.
0
-2147483648…
2147483647
32-bit data.
-
Data storage parameter 17.
0
-32768…32767
16-bit data.
1 = 1
Data storage parameter 18.
0
-32768…32767
16-bit data.
1 = 1
Data storage parameter 19.
0
-32768…32767
16-bit data.
1 = 1
Data storage parameter 20.
0
-32768…32767
16-bit data.
1 = 1
49
Communication settings for the control panel port on the
drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note:
For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
1
1…32
Node ID.
1 = 1
Defines the transfer rate of the link.
38.4 kbps
38.4 kbit/s.
1
57.6 kbps
57.6 kbit/s.
2
86.4 kbps
86.4 kbit/s.
3
115.2 kbps
115.2 kbit/s.
4
230.4 kbps
230.4 kbit/s.
5
Sets a timeout for control panel (or PC tool) communication. If
a communication break lasts longer than the timeout, the
action specified by parameter
is taken.
10.0 s
0.3…3000.0 s
Panel/PC tool communication timeout.
10 = 1 s
Selects how the drive reacts to a control panel (or PC tool)
communication break.
No action
No action taken.
0
Fault
Drive trips on
1
Last speed
Drive generates an
warning and freezes the
speed to the level the drive was operating at. The speed is
determined on the basis of actual speed using 850 ms low-
pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...