Fault tracing 419
A7C1
FBA A communication
Programmable warning:
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups
,
,
Check cable connections.
Check if communication master is able to
communicate.
A7CE EFB comm loss
Programmable warning:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
A7EE Panel loss
Programmable warning:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Check mounting platform if being used.
Disconnect and reconnect the control
panel.
A88F
Cooling fan
Maintenance timer limit
exceeded.
Replace the drive cooling fan.
Parameter
shows the running time of the cooling
fan.
A8A0
AI supervision
Analog signal is beyond limits. Check the signal level, input wiring, and
the defined limits.
A8A1
RO life warning
The relay has changed states
more than the recommended
number of times.
Change the control board or stop using
the relay output.
0001 Relay output 1
Change the control board or stop using
relay output 1.
0002 Relay output 2
Change the control board or stop using
relay output 2.
0003 Relay output 3
Change the control board or stop using
relay output 3.
A8A2
RO toggle warning
The relay output is changing
states faster than
recommended, eg. if a fast
changing frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
Replace the signal connected to the relay
output source with a less frequently
changing signal.
0001 Relay output 1
Select a different signal with parameter
.
0002 Relay output 2
Select a different signal with parameter
.
Code
(hex)
Warning / Aux. code
(
aux code visible only
on assistant control
panel and drive
composer
)
Cause
What to do
0001 – AI1 less minimum
0003 – AI2 less minimum
0002 – AI1 greater maximum
0004 – AI2 greater maximum
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...