332 Parameters
Source selection (see
). -
…
…
…
…
See parameter
.
53
Selection of data to be transferred from fieldbus controller to
drive through fieldbus adapter A.
Note:
32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
select data to be transferred from
the fieldbus controller to the drive through fieldbus adapter A.
None
None.
0
CW 16bit
Control Word (16 bits)
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
CW2 16bit
Control Word 2 (16 bits)
21
Source selection (see
). -
…
…
…
…
See parameter
58
Configuration of the embedded fieldbus (EFB) interface.
See also chapter
Fieldbus control through the embedded
(page
).
Enables/disables the embedded fieldbus interface and
selects the protocol to use.
None
None (communication disabled).
0
Modbus RTU
Embedded fieldbus interface is enabled and uses the Modbus
RTU protocol.
1
Displays the protocol ID and revision.
This parameter is read-only.
-
Protocol ID and revision.
1 = 1
Defines the node address of the drive on the fieldbus link.
Values 1…247 are allowable. Two devices with the same
address are not allowed on-line.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
1
0…255
Node address (values 1…247 are allowed).
1 = 1
Selects the transfer rate of the fieldbus link.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Autodetect
Baud rate detected automatically
0
4.8 kbps
4.8 kbit/s.
1
9.6 kbps
9.6 kbit/s.
2
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...