354 Parameters
Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
0b0000
0b0000…0b1111
Hardware options configuration word.
1 = 1
Specifies more hardware-related options that require
differentiated parameter defaults. See parameter
.
WARNING!
An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
0b0000
0b0000…0b1111
Hardware options configuration word.
1 = 1
Selects the fan control type. The fan control functionality
enables heat dissipation from the drive and avoids dust
accumulation in the drive.
Auto
Controls the fan automatically according to the temperature
changes of the drive.
0
Always on
Fan runs continuously with the maximum speed (50Hz).
1
96
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under
View
–
Settings
–
Drive default language
.)
Not selected
Not selected
None.
0
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
Supply frequency
60 Hz
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
on page
.0 = 50 Hz.
1 = 60 Hz.
1…12
Reserved
13
du/dt filter
activation
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
14…15 Reserved
Bit
Name
Value
0...4
Reserved
5
Bypass present
1 = Bypass is used.
6
Cabinet drive
0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
7
Reserved
0 = Inactive, 1 = Active. Only for drive frames R6 or larger.
8...15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...