Parameters 363
Defines the relative output voltage boost at zero speed (IR
compensation). The function is useful in applications with a
high break-away torque where vector control cannot be
applied.
See also section
IR compensation for scalar motor control
on
page
.
Typical IR compensation values are shown below.
WARNING!
Set IR compensation value as low as
possible. Large IR compensation value can lead to
overheating of the motor and damage to the drive, if
operated for longer periods at low speed.
3.50%
0.00…50.00%
Voltage boost at zero speed in percent of nominal motor
voltage.
1 = 1%
Selects the form for the
U
/
f
(voltage to frequency) ratio below
field weakening point. For scalar control only.
Linear
Linear ratio for constant torque applications.
0
Squared
Squared ratio for centrifugal pump and fan applications.
With squared U/f ratio the noise level is lower for most
operating frequencies.
1
No.
Name/Value
Description
Def/FbEq16
U
/
U
N
(%)
f
(Hz)
Field weakening point
Relative output voltage. No
IR compensation.
Relative output voltage. IR
compensation set to 15%.
15%
100%
50% of nominal
frequency
3-phase 380…415V drives
P
N
(kW) 0, 37 0, 75 1, 1 2, 2
4
7, 5
15
37 132
IR
compen
-sation
(%)
3, 5 3, 5 3, 2 2, 5
2
1, 5
1.3
1.1 0.6
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...