Control macros 151
Terminal sizes
• (frames R0…R8): 0.14…1.5 mm
2
(all terminals)
• Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)…20 mA,
R
in
< 500 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm]
input as selected with parameter
12.15 AI1 unit selection
.
2)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm]
input as selected with parameter
12.25 AI2 unit selection
.
3)
Total load capacity of the auxiliary voltage 24V (X2:10) = 6.0 W (250 mA /
24 V). User can use this source for either of the I/O connections (DI1... DI2- RO1 or
DI3...DI6 - RO2~RO3).
4)
Connected with jumpers at the factory.
5)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
6)
Can be used to set up pressure alarm warning.
7)
Can be used for cold start prevention with connection to ‘temperature reached’
output of temperature controller or PLC
8)
Input signal
9)
Output signal
10)
For R0...R2 frames only
11)
The start in forward direction is connected to digital input DI1 and the start/stop in
reverse direction is connected to digital input DI2.
12)
The start is connected to digital input DI1 and the torque reversal is connected to
digital input DI2.
13)
EXT1 is configured for speed control and EXT2 is configured for torque control in
both drive 1 and drive 2.
For information on cable connection and drive operation, see
Control Connections
in
the
hardware manual (3AXD50000044998)
.
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...