306 Parameters
PID output
PID controller output.
2
Selects the source that determines whether process PID
parameter set 1 (parameters
…
) or set 2 (group
) is used.
PID set 1
0. Process PID parameter set 1 in use.
0
PID set 2
1. Process PID parameter set 2 in use.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Timed function 1
18
Timed function 2
19
Timed function 3
20
Supervision 1
21
Supervision 2
22
Supervision 3
23
Source selection (see
). -
Prevention of PID integration term increase for PID set 1.
No
Increase prevention not in use.
0
Limiting
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Ext PID min lim
The process PID integration term is not increased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
2
Ext PID max lim
The process PID integration term is not increased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
3
Source selection (see
). -
Prevention of PID integration term decrease for PID set 1.
No
Decrease prevention not in use.
0
Limiting
The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is valid
for the PID set 1.
1
Ext PID min lim
The process PID integration term is not decreased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
2
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...