Parameters 197
Displays the value of AO2 in mA.
This parameter is read-only.
0.000
0.000 … 22.000 mA Value of AO2.
1000 = 1 mA
Selects a signal to be connected to analog output AO2.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
For the selections, see parameter
Forced value that can be used instead of the selected output
signal. See parameter
0.000 mA
0.000 … 22.000 mA Forced value for AO2.
1000 = 1 mA
Defines the filtering time constant for analog output AO2. See
parameter
.
0.100 s
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
Defines the real minimum value of the signal (selected by
parameter
) that corresponds to the
minimum required AO2 output value (defined by parameter
). See parameter
about the AO automatic scaling.
Programming
as the maximum value and
as the
minimum value inverts the output.
0.0
-32768.0…32767.0
Real signal value corresponding to minimum AO2 output
value.
1 = 1
No.
Name/Value
Description
Def/FbEq16
I
AO2
(mA)
Signal
(real)
selected by
I
AO2
(mA)
Signal
(real)
selected by
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...