The following table shows the values of selected DC voltage levels. The drive DC
voltage limits are calculated based on the parameter
.
Notes:
• parameter
is the estimated voltage during
start-up of the drive and is not continuously updated during the time lim eit.
• The absolute voltages vary according to the drive/inverter type and AC supply
voltage range.
DC Voltage level
[V]
AC supply voltage range [V]
380…415
AC supply voltage range [V]
440…480
Automatic/Not selected
Overvoltage fault
limit
842
842
842
Overvoltage
control limit
779
779
779
Internal brake
chopper start
limit
779
779
779
Internal brake
chopper stop
limit
759
759
759
Overvoltage
warning limit
745
745
745
Undervoltage
warning limit
0.85×1.41×par
value
1)
0.85×1.41×par
value
1)
0.85×1.41×par
value
1)
0.85×1.35×380 = 436
2)
0.85×1.35×440 = 463
2)
0.85×1.35×440 = 463
2)
Undervoltage
control limit
0.78×1.41×par
value
1)
value
1)
0.78×1.41×par
value
1)
0.78×1.35×380 = 400
2)
0.78×1.35×440 = 463
2)
0.78×1.35×440 = 463
2)
Charging relay
closing limit
0.78×1.41×par
value
1)
0.78×1.41×par
value
1)
0.78×1.41×par
value
1)
0.78×1.35×380 = 400
2)
0.78×1.35×440 = 463
2)
0.78×1.35×440 = 463
2)
Charging relay
opening limit
0.73×1.41×par
value
1)
0.73×1.41 ×par
value
1)
value
1)
0.73×1.35×380 = 374
2)
0.73×1.35×440 = 433
2)
0.73×1.35×440 = 433
2)
Undervoltage
fault limit
0.73×1.41×par
value
1)
value
1)
0.73×1.41×par
value
1)
0.73×1.35×380 = 374
2)
0.73×1.35×440 = 433
2)
0.45×1.35×440 = 433
2)
DC voltage at
upper bound of
supply voltage
range (
U
DCmax
)
560
648
648
DC voltage at
lower bound of
supply voltage
range (
U
DCmin
)
513
594
594
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...