314 Parameters
44
Configuration of mechanical brake control.
See also section
).
Displays the mechanical brake control status word.
This parameter is read-only.
0b0000
0b0000…0b1111
Mechanical brake control status word.
1 = 1
Activates/deactivates (or selects a source that
activates/deactivates) the mechanical brake control logic.
0 = Brake control inactive
1 = Brake control active
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Timed function 1
18
Timed function 2
19
Timed function 3
20
Supervision 1
24
Supervision 2
25
Supervision 3
26
Source selection (see
). -
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Open command
Close/open command to brake actuator (0 = close, 1 = open).
Connect this bit to desired output.
1
Opening torque
request
1 = Opening torque requested from drive logic.
2
Hold stopped
request
1 = Hold requested from drive logic
3
Ramp to stopped
1 = Ramping down to zero speed requested from drive logic
4
Enabled
1 = Brake control is enabled
5
Closed
1 = Brake control logic in
state
6
Opening
1 = Brake control logic in
state
7
Open
1 = Brake control logic in
state
8
Closing
1 = Brake control logic in
state
9…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...