448 Fieldbus control through the embedded fieldbus interface (EFB)
Control Word for the DCU Profile
The embedded fieldbus interface writes the fieldbus Control Word as is to the drive
Control Word bits 0 to 15. Bits 16 to 32 of the drive Control Word are not in use.
8
JOGGING_1
1
Request running at Jogging 1 speed.
Note:
This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
9
JOGGING_2
1
Request running at Jogging 2 speed.
Note:
This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
10
REMOTE_
CMD
1
Fieldbus control d.
0
Control Word <> 0 or Reference <> 0: Retain last Control
Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control d.
Reference and deceleration/acceleration ramp are
locked.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External Control Location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
12
USER_0
Writable control bits that can be combined with drive logic
for application-specific functionality.
13
USER_1
14
USER_2
15
USER_3
Bit
Name
Value
State/Description
0
STOP
1
Stop according to the Stop Mode parameter or the stop
mode request bits (7…9).
0
(no op)
1
START
1
Start the drive.
0
(no op)
Bit
Name
Value
STATE/Description
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...