344 Parameters
The control program compares the absolute value of
parameter
to the deadband range
defined by this parameter. If the absolute value is within the
deadband range for the time period defined by parameter
, PID's deadband mode is activated
and
bit 9
is set. Then
PID's output is frozen and
bit 2
is set.
If the absolute value is equal or greater than the deadband
range, PID's deadband mode is deactivated.
0.0
0.0…200000.0
Range
1 = 1
Defines the deadband delay for the deadband function. See
parameter
.
0.0 s
0.0…3600.0 s
Delay
1 = 1 s
See parameter
See parameter
.
See parameter
. -
Selects the unit for process PID setpoint, feedback and
deviation.
User text
User text
0
%
%
1
bar
bar
2
kPa
kPa
3
Pa
Pa
4
psi
psi
5
CFM
CFM
6
inH
2
O
inH
2
O
7
°C
°C
8
°F
°F
9
mbar
mbar
10
m
3
/h
m
3
/h
11
dm
3
/h
dm
3
/h
12
I/s
I/s
13
I/min
I/min
14
I/h
I/h
15
m
3
/s
m
3
/s
16
m
3
/m
m
3
/m
17
km
3
/h
km
3
/h
18
gal/s
gal/s
19
ft
3
/s
ft
3
/s
20
ft
3
/m
ft
3
/m
21
ft
3
/h
ft
3
/h
22
ppm
ppm
23
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...