220 Parameters
Selects a mathematical function between the reference
sources selected by parameters
. See diagram at
.
Ref1
is used as speed
reference 1 as such (no function applied).
0
Add (ref1 + ref2)
The sum of the reference sources is used as speed reference
1.
1
Sub (ref1 - ref2)
The subtraction ([
] - [
]) of the reference sources is used as speed reference 1.
2
Mul (ref1 × ref2)
The multiplication of the reference sources is used as speed
reference 1.
3
Min (ref1, ref2)
The smaller of the reference sources is used as speed
reference 1.
4
Max (ref1, ref2)
The greater of the reference sources is used as speed
reference 1.
5
Determines how constant speeds are selected, and whether
the rotation direction signal is considered or not when
applying a constant speed.
0b0001
0b0000...0b1111
Constant speed configuration word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Constant speed
mode
1 = Packed: 7 constant speeds are selectable using the three sources
defined by parameters
,
and
0 = Separate: Constant speeds 1, 2 and 3 are separately activated by
the sources defined by parameters
,
respectively.
In case of conflict, the constant speed with the smaller number takes
priority.
1
Direction
enable
1 = Start dir: To determine running direction for a constant speed, the
sign of the constant speed setting (parameters
) is
multiplied by the direction signal (forward: +1, reverse: -1). This
effectively allows the drive to have 14 (7 forward, 7 reverse) constant
speeds if all values in
…
are positive.
WARNING:
If the direction signal is reverse and the active
constant speed is negative, the drive will run in the forward
direction.
0 = Accord Par: The running direction for the constant speed is
determined by the sign of the constant speed setting (parameters
…
2…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...