Fault tracing 427
4991
Safe motor
temperature
The CPTC-02 module
indicates overtemperature:
• motor temperature is too
high, or
• the thermistor is in
shortcircuit.
Check the cooling of the motor.
Check the motor load and drive ratings.
Check the wiring of the temperature
sensor. Repair wiring if faulty.
Measure the resistance of the sensor.
Replace the sensor if faulty.
5080
Fan
Cooling fan is stuck or
disconnected.
See
(page
).
5081
Auxiliary fan broken
An auxiliary cooling fan is
stuck or disconnected.
Check auxiliary fan(s) and connection(s).
Replace fan if faulty.
0001 Auxiliary fan 1 broken.
0002 Auxiliary fan 2 broken.
5089
SMT circuit
malfunction
Safe motor temperature fault is
generated and STO
event/fault/warning is not
generated.
Check connection between the relay
output of the module and the STO
terminal.
5090
STO hardware failure
STO hardware diagnostics has
detected hardware failure.
Contact your local ABB representative for
hardware replacement.
5091
Safe torque off
Programmable fault:
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is broken
during start or run.
Check safety circuit connections. For
more information, see chapter
The Safe
torque off function
in the
Hardware
manual
of the drive and description of
parameter
(page
).
Check the value of parameter
5092
PU logic error
Power unit memory has
cleared.
Contact your local ABB representative.
5093
Rating ID mismatch
The hardware of the drive does
not match the information
stored in the memory. This
may occur eg. after a firmware
update.
Cycle the power to the drive. You may
have to be repeat this.
5094
Measurement circuit
temperature
Problem with internal
temperature measurement of
the drive.
Contact your local ABB representative.
5095
Redundant
measurement
Duplicated measurements are
beyond limits.
Contact ABB.
5096
Overtemperature hw
Excessive hardware
temperature.
Contact your local ABB representative.
5098
I/O communication
loss
Communication failure to
standard I/O.
Try resetting the fault or cycle the power
to the drive.
5681
PU communication
Communication errors
detected between the drive
control unit and the power unit.
Check the connection between the drive
control unit and the power unit.
Check the value of parameter
5682
Power unit lost
Connection between the drive
control unit and the power unit
is lost.
Check the connection between the
control unit and the power unit.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...