266 Parameters
Selects how the drive reacts when an auxiliary fan problem is
detected.
Certain drive types (especially those protected to IP55) have
an auxiliary fan built into the front cover as standard.
If it is necessary to operate the drive without the front cover
(for example, during commissioning), you can set the
parameter to value No action within two minutes from power-
up to temporarily suppress the fault or warning. Return the
value to Fault or Warning afterwards.
This parameter is applicable only for frames R3 or larger.
On frame sizes R3…R5, the auxiliary fan is attached to
connector X10 and on frame sizes R6 and larger to connector
X16.
Fault
The drive trips on fault
.
The fault is suppressed for two minutes after power-up.
0
Warning
The drive generates a warning
The warning is suppressed for two minutes after power-up.
1
No action
No action taken
2
32
Configuration of signal supervision functions 1…6.
Six values can be chosen to be monitored; a warning or fault
is generated whenever predefined limits are exceeded.
See also section
(page
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note:
This word is independent of the drive actions defined
.
0b000
0b0000…0b1111
Signal supervision status word.
1 = 1
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter
) is compared
to its low and high limits (
respectively). The
action to be taken when the condition is fulfilled is selected by
Disabled
Signal supervision 1 not in use.
0
Low
Action is taken whenever the signal falls below its low limit.
1
High
Action is taken whenever the signal rises above its high limit.
2
Abs low
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit.
3
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Supervision 1 active
is outside its limits.
1
Supervision 2 active
is outside its limits.
2
Supervision 3 active
is outside its limits.
3
Supervision 4 active
is outside its limits.
4
Supervision 5 active
is outside its limits.
5
Supervision 6 active
is outside its limits.
6…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...