Program features 35
Two external control locations, EXT1 and EXT2, are available. The user can select
the sources of the start and stop commands separately for each location by setting
parameters
. Selection between EXT1 and EXT2 is done via any binary
source such as a digital input or fieldbus control word (parameter
). The source of reference is selectable for each operating mode separately.
Communication fail functionality
The communication fail functionality ensures continuous process without
interruptions. If there is a communication loss, the drive automatically changes the
control location from EXT1 to EXT2. This enables process to be controlled, for
example, with the drive PID controller. When the original control location recovers,
the drive automatically switches control back to the communication network (EXT1).
EXT1/EXT2 selection for speed control
Default =
Input 1
Input 2
Input 3
Input 1
Input 2
Input 3
Function
or a math.
function of
Input 1
Input 2
Input 3
Input 1
Input 2
Input 3
Function
or a math.
function of
Select
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...