Fault tracing 429
800A The application contains an
unknown target (system)
library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
64A1
Internal file load
File read error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative.
64A4
Rating ID fault
Rating ID load error.
Contact ABB.
64A6
Adaptive program
Fault in adaptive program.
Check the fault code extension.
64B1
Internal SSW fault
A fatal error in the power-up
phase of System Software
(SSW).
SSW runs in partial functionality mode.
64B2
User set fault
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64B3
Macro
parameterization error
Macro parameterization failed,
eg. Parameter default
value that cannot be changed
has been attempted to write.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
. Retry.
6591
Backup/Restore
timeout
During backup creating or
restoring operation a panel or
PC-tool has failed to
communicate with the drive as
part of this operation.
Check panel or PC-tool communication
and if it is still in backup or restore state.
65A1
FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
and
.
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
1 – Starting OS time tick failed
5 – Initializing WoRm volumes failed
2 – Creating system tasks failed
6 – Loading FPGA configuration failed
3 – Initializing file system failed
7 – Loading application program failed
4 – Checking file system failed
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...