background image

The instructions do not purport to cover all details or variations in equipment nor to provide for every possible 
contingency to be met in connection with installation, operation or maintenance. Should further information be 
desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the 
matter should be referred to the GE company.

AF-600 FP are trademarks of the General Electric Company.

GE
41 Woodford Avenue
Plainville, CT 06062

www.geindustrial.com/drives

130R0359 

*MG11S502*

DET-620D

GE 

Industrial Solutions

AF-600 FP

TM

Fan & Pump Drive

Programming Guide

AF-600 FP

TM

 F

an and Pump Driv

e Pr
ogramming Guide

 

 

 

 

 

 

                                        DE

T-620D

Summary of Contents for Ecomagination AF-600 FP

Page 1: ...d or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE company AF 600 FP are trademarks of the General Electric Company GE 41 Woodford Avenue Plainville CT 06062 www geindustrial com drives 130R0359 MG11S502 DET 620D GE Industrial Solutions AF 600 FPTM Fan Pump Drive Programming Guide AF 600 FP TM Fan and Pump D...

Page 2: ...nverters 15 2 1 3 Parameter Set Up 16 2 1 4 Quick Menu Mode 16 2 1 5 Macros 17 2 1 6 Main Menu Mode 21 2 1 7 Parameter Selection 21 2 1 8 Changing Data 21 2 1 9 Changing a Text Value 22 2 1 10 Changing a Group of Numeric Data Values 22 2 1 11 Value Step by step 22 2 1 12 Read out and Programming of Indexed Parameters 22 2 1 13 Restore to Default Settings 23 3 Parameter Description 24 3 1 K Keypad ...

Page 3: ...3 3 26 B Braking Functions 194 4 Troubleshooting 197 4 1 Status Messages 197 4 1 1 Alarms and Warnings 197 4 1 2 Alarm Words 200 4 1 3 Warning Words 201 4 1 4 Extended Status Words 202 4 2 Fault Messages 203 5 Parameter Lists 210 5 1 Parameter Options 210 5 1 2 K Keypad Set up 211 5 1 3 F Fundamental Parameters 212 5 1 4 E Digital In Outs 213 5 1 5 C Frequency Control Functions 214 5 1 6 P Motor D...

Page 4: ...t Status 226 5 1 20 AP HVAC Appl Param 227 5 1 21 FB Fire Bypass Operation 228 5 1 22 T Timed Functions 228 5 1 23 CL PID Closed Loop 229 5 1 24 XC Ext PID Closed Loop 230 5 1 25 PC Pump Controller 232 5 1 26 LC Logic Controller 233 5 1 27 B Braking Functions 234 Index 235 Contents AF 600 FP Programming Guide DET 620D 03 2016 All rights reserved 3 ...

Page 5: ...e inability to use information contained in this manual even if advised of the possibility of such damages In particular GE is not responsible for any costs including but not limited to those incurred as a result of lost profits or revenue loss or damage of equipment loss of computer programs loss of data the costs to substitute these or any claims by third parties GE reserves the right to revise ...

Page 6: ...ak away Torque ηDRIVE The efficiency of the frequency converter is defined as the ratio between the power output and the power input Start disable command A stop command belonging to Group 1 control commands see Table 1 2 Stop command A stop command belonging to Group 1 control commands see Table 1 2 1 5 4 References Advanced Vector Control If compared with standard voltage frequency ratio control...

Page 7: ...ned events are evaluated as true by the Logic Controller Parameter group LC lsb Least significant bit msb Most significant bit MCM Short for Mille Circular Mil an American measuring unit for cable cross section 1 MCM 0 5067mm2 On line Off line Parameters Changes to on line parameters are activated immediately after the data value is changed Press OK to activate changes to off line parameters Proce...

Page 8: ... Ensure correct grounding of the equipment by a certified electrical installer Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains Check that the mains supply has been disconnected and that the necessary time has elapsed before removing motor and mains plugs The frequency converter has more voltage sources than L1 L2 and L3 when load sharing l...

Page 9: ...software are allowed NOTICE Hazardous situations shall be identified by the machine builder integrator who is responsible for considering necessary preventive measures Additional monitoring and protective devices may be included always according to valid national safety regulations for example law on mechanical tools regulations for the prevention of accidents Protection mode Once a hardware limit...

Page 10: ...y cables If this occurs it may be necessary to break the shield or insert a 100 nF capacitor between shield and chassis The digital and analog inputs and outputs must be connected separately to the common inputs terminal 20 55 39 of the frequency converter to avoid ground currents from both groups to affect other groups For example switching on the digital input may disturb the analog input signal...

Page 11: ...ty of control terminals Illustration 1 3 PNP Source Illustration 1 4 NPN Sink NOTICE Control cables must be screened armoured Illustration 1 5 Control Cables Introduction 10 03 2016 All rights reserved DET 620D 1 1 ...

Page 12: ...perator data lines displaying data and variables defined or selected by the user Press Status to add 1 extra line c Status line Status messages displaying text Illustration 2 1 LCP The display is divided into 3 sections Top section a shows the status when in Status mode or up to 2 variables when not in Status mode and in the case of alarm warning The number of the active set up selected as the act...

Page 13: ...yed operating variables 1 1 1 2 1 3 2 and 3 See the operating variables shown in the display in Illustration 2 2 1 1 1 2 and 1 3 are shown in small size 2 and 3 are shown in medium size Illustration 2 2 Example of Status Display I Status display II See the operating variables 1 1 1 2 1 3 and 2 shown in the display in Illustration 2 3 In the example speed motor current motor power and frequency are...

Page 14: ...required for most applications including Most VAV and CAV supply and return fans Cooling tower fans Primary secondary and condenser water pumps Other pump fan and compressor applications Among other features it also includes parameters for selecting which variables to display in the keypad digital preset speeds scaling of analog references closed loop single zone and multi zone applications and sp...

Page 15: ...e 4 navigation keys are used to navigate between the different options available in the Quick Menu Main Menu and Alarm Log Press the keys to move the cursor OK Press OK to select a parameter marked by the cursor and for enabling the change of a parameter Illustration 2 11 Navigation Keys Operation keys Operation keys for local control are found at the bottom of the keypad Illustration 2 12 Operati...

Page 16: ...d as 1 Enable or 0 Disable via parameter K 43 Reset Button on Keypad The parameter shortcut can be carried out by pressing the Main Menu key for 3 s The parameter shortcut allows direct access to any parameter 2 1 2 Quick Transfer of Parameter Settings between Multiple Frequency Converters Once the set up of a frequency converter is complete store the data in the keypad or on a PC via Drive Contro...

Page 17: ... Highlighted area indicates digit selected for change 8 Press Cancel to disregard change or press OK to accept change and enter the new setting Example of changing parameter data Assume F 07 Accel Time 1 is set to 6 s and you want to change it to 10 s Use the following procedure 1 Press Quick Menu 2 Press to select Quick Start 3 Press OK 4 With find par F 07 Accel Time 1 5 Press OK 6 Use the arrow...

Page 18: ...ends on the selections made in parameter K 02 Motor Speed Unit and parameter K 03 Regional Settings The default settings of parameter K 02 Motor Speed Unit and parameter K 03 Regional Settings depend on which region of the world the frequency converter is supplied to but can be reprogrammed as required 2 1 5 Macros The Macros provide quick and easy access to all parameters required for most HVAC a...

Page 19: ...nd AP 62 Broken Belt Delay Illustration 2 19 General Settings Options 5 Press OK Illustration 2 20 Parameter AN 50 Terminal 42 Output Selected 6 Press and to change the delay time Illustration 2 21 Setting a Parameter How to Program 18 03 2016 All rights reserved DET 620D 2 2 ...

Page 20: ...ode Parameter AP 84 Speed at No Flow Hz Parameter F 24 Holding Time Parameter AP 85 Speed at Design Point RPM Parameter H 80 Function at Stop Parameter AP 86 Speed at Design Point Hz Parameter B 00 DC Hold Current Parameter AP 87 Pressure at No Flow Speed Parameter H 08 Reverse Lock Parameter AP 88 Pressure at Rated Speed Parameter AP 89 Flow at Design Point Parameter AP 90 Flow at Rated Speed Par...

Page 21: ...alue Parameter CL 94 PID Integral Time Parameter AN 16 Terminal 53 Filter Time Constant Parameter AN 17 Terminal 53 Live Zero Parameter AN 20 Terminal 54 Low Voltage Parameter AN 21 Terminal 54 High Voltage Parameter AN 22 Terminal 54 Low Current Parameter AN 23 Terminal 54 High Current Parameter AN 24 Terminal 54 Low Ref Feedb Value Parameter AN 25 Terminal 54 High Ref Feedb Value Parameter AN 26...

Page 22: ...number Parameter group K Keypad Set up F Fundamental Parameters E Digital In Outs C Frequency Control Functions P Motor Data H High Perf Parameters AN Analog In Out SP Special Functions O Options comms AO Analog I O Option DN DeviceNet PB PROFIBUS LN LonWorks BN BACnet ID Drive Information DR Data Readouts LG Logs I O Opt Status AP HVAC Appl Param Group number Parameter group FB Fire Bypass Operat...

Page 23: ...by step This applies to Parameter P 07 Motor Power kW Parameter F 05 Motor Rated Voltage Parameter F 04 Base Frequency The parameters are changed both as a group of numeric data values and as numeric data values that are infinitely varying 2 1 12 Read out and Programming of Indexed Parameters Parameters are indexed when placed in a rolling stack Parameter ID 30 Alarm Log Error Code to parameter ID...

Page 24: ...ay Parameter O 37 Maximum Inter Char Delay Parameter ID 00 Operating hours to parameter ID 05 Over Volt s Parameter ID 20 Historic Log Event to parameter ID 22 Historic Log Time Parameter ID 30 Alarm Log Error Code to parameter ID 32 Alarm Log Time Manual restore 1 Disconnect from mains and wait until the display turns off 2 Press Status Main Menu OK at the same time while power up for keypad Grap...

Page 25: ...d Unit and parameter K 03 Regional Settings depend on which region of the world the frequency converter is supplied to Reprogram the settings as required The settings not used are made invisible 0 Interna tional Sets parameter P 07 Motor Power kW units to kW and the default value of parameter F 04 Base Frequency 50 Hz 1 US Sets parameter P 02 Motor Power HP units to hp and the default value of par...

Page 26: ...efore the new values are reflected via the fieldbus K 10 Active Set up Option Function Select the set up in which the frequency converter is to operate Use parameter K 51 Set up Copy to copy a set up to 1 or all other set ups To avoid conflicting settings of the same parameter within 2 different set ups link the set ups using parameter K 12 This Set up Linked to Stop the frequency converter before...

Page 27: ... Set up Linked to Option Function set ups 1 and 2 to indicate that all not changeable during operation parameters are now the same in set up 1 and set up 2 If there are changes to a not changeable during operation parameter for example parameter P 30 Stator Resistance Rs in set up 2 they are also changed automatically in set up 1 A switch between set up 1 and set up 2 during operation is now possi...

Page 28: ...out parameter K 31 Min Value of Custom Readout and parameter K 32 Max Value of Custom Readout 1210 Power kW Actual power consumed by the motor in kW 1211 Power hp Actual power consumed by the motor in HP 1212 Motor Rated Voltage Voltage supplied to the motor 1213 Frequency Motor frequency i e the output frequency from the frequency converter in Hz 1214 Motor Current Phase current of the motor meas...

Page 29: ... Comm Option STW Extended fieldbus communication option status word 1285 Drive Port CTW 1 Control word CTW received from the Bus Master 1286 Drive Port REF 1 Status word STW sent to the Bus Master 1290 Alarm Word One or more alarms in a Hex code used for serial communications 1291 Alarm Word 2 One or more alarms in a Hex code used for serial communications 1292 Warning Word One or more warnings in...

Page 30: ...ch require changing on a regular basis for example for plant maintenance reasons or by an OEM to enable simple commissioning of their equipment 3 1 4 K 3 Keypad Custom Readout It is possible to customize the display elements for various purposes Custom readout Value proportional to speed linear squared or cubed depending on unit selected in parameter K 30 Unit for Custom Readout Display text Text ...

Page 31: ...adratic and cubic units the minimum value is 0 0 00 Custom ReadoutUnit 999999 99 100 00 CustomRea doutUnit K 32 Max Value of Custom Readout Range Function 100 Custom ReadoutUnit par K 31 999999 99 CustomRea doutUnit This parameter sets the maximum value to be shown when the speed of the motor has reached the set value for parameter F 17 Motor Speed High Limit RPM or parameter F 15 Motor Speed High...

Page 32: ...Quick Start Menu define the password in parameter K 65 Quick Menu Password Otherwise define the password in parameter K 60 Main Menu Password K 41 Off Button on Keypad Option Function 0 Disabled Select to disable the key 1 Enabled Off key is enabled 2 Password Protection Avoid unauthorized stop If parameter K 41 Off Button on Keypad is included in Quick Start Menu define the password in parameter ...

Page 33: ...in Menu w o Password is set to 0 Full access this parameter is ignored K 61 Access to Main Menu w o Password Option Function 0 Full access Disables password defined in parameter K 60 Main Menu Password 1 Keypad Read only Prevents unauthorized editing of Main Menu parameters 2 Keypad No access Prevents unauthorized viewing and editing of Main Menu parameters 3 Bus Read only 4 Bus No access 5 All Re...

Page 34: ...h 1 12 h K 74 DST Summertime Option Function Select how to handle daylight saving time summertime For manual setting of DST summertime enter the start date and end date in parameter K 76 DST Summertime Start and parameter K 77 DST Summertime End 0 Off 2 Manual K 76 DST Summertime Start Range Function 0 0 0 Sets the date and time when DST summertime starts The date is programmed in the format selec...

Page 35: ...ional working days that would normally be non working days according to parameter K 81 Working Days K 89 Date and Time Readout Range Function 0 0 25 Shows the current date and time The date and time is updated continuously The clock does not begin counting until a setting different from default has been made in parameter K 70 Date and Time Parameter Description 34 03 2016 All rights reserved DET 6...

Page 36: ... in both hand on mode and auto on mode NOTICE When set to 2 Local the frequency converter starts with this setting again after a power down F 03 Max Output Frequency 1 Range Function 100 0 Hz 1 590 Hz NOTICE This parameter cannot be adjusted while the motor is running Enter the maximum output frequency value Parameter F 03 Max Output Frequency 1 specifies the absolute limit on the frequency conver...

Page 37: ...optimum U f characteristic The motor size determines the frequency range within which this parameter is active Motor size kW Change over Hz 0 25 7 5 10 11 45 5 55 550 3 4 Table 3 3 Low Speed Load Compensation Illustration 3 4 Low Speed Load Compensation 3 2 2 F 1 Fundamental Parameters 1 NOTICE When using multiple motors the electronic thermal relay on the frequency converter cannot be used to pro...

Page 38: ...ass 20 motor overload protection in accordance with NEC Illustration 3 5 Thermal Motor Protection NOTICE If the temperature of the motor is monitored through a thermistor or a KTY Sensor the PELV is not complied with in case of short circuits between motor windings and the sensor To comply with PELV isolate the sensor appropriately NOTICE The Electronic Overload timer function does not work when p...

Page 39: ...load Profile 3 2 3 3 Klixon The Klixon type thermal circuit breaker uses a KLIXON metal dish At a predetermined overload the heat caused by the current through the disc causes a trip Using a digital input and 24 V as supply Example The frequency converter trips when the motor temperature is too high Parameter set up Set parameter F 10 Electronic Overload to 2 Thermistor Trip Set parameter F 12 Mot...

Page 40: ... RPM Range Function NOTICE Maximum output frequency cannot exceed 10 of the carrier frequency parameter F 26 Motor Noise Carrier Freq Enter the maximum limit for motor speed in RPM The motor speed high limit can be set to correspond to the manufacturer s maximum rated motor The motor speed high limit must exceed the setting in parameter F 18 Motor Speed Low Limit RPM The parameter name appears as ...

Page 41: ...ulation This extra voltage results in an extra torque of 10 12 in the middle of the oversyncronous range from 0 at nominal speed rising to approxi mately 12 at double nominal speed 3 2 6 F 4 Fundamental Parameters F 40 Torque Limiter Driving Range Function 110 0 0 1000 0 Enter the maximum torque limit for motor operation The torque limit is active in the speed range up to and including the nominal...

Page 42: ... 3 11 Preset Relative Reference Illustration 3 12 Actual Reference 3 2 9 F 9 Digital Potentiometer The digital potentiometer function allows the user to increase or decrease the actual reference by adjusting the set up of the digital inputs using the functions INCREASE DECREASE or CLEAR To activate the function at least one digital input must be set up to INCREASE or DECREASE F 90 Step Size Range ...

Page 43: ...igital pot meter is used for fine tuning of the resulting reference F 95 Accel Decel Ramp Delay Range Function 0 000 0 000 0 000 Enter the delay required from activation of the digital potentiometer function until the frequency converter starts to ramp the reference With a delay of 0 ms the reference starts to ramp as soon as increase decrease is activated See also parameter F 91 Accel Decel Time ...

Page 44: ... the input the reaction described above will be delayed with the time set in parameter AP 00 External Interlock Delay 8 Start Default Digital input 18 Select start for a start stop command Logic 1 start logic 0 stop 9 Latched start The motor starts if a pulse is applied for min 2 ms The motor stops when Stop inverse is activated 10 Reversing Default Digital input 19 Change the direction of motor s...

Page 45: ...be logic 1 on one of the terminals for the function to be carried out The digital output signal for Run Request Start 8 Jog 14 or Freeze output 20 will not be affected by Run Permissive NOTICE If no Run Permissive signal is applied but either Run Jog or Freeze commands is activated the status line in the display will show either Run Requested Jog Requested or Freeze Requested 53 Hand start A signa...

Page 46: ... 43 Current Limit during ramping See decel time in parameter E 11 Decel Time 2 par E 10 tacc nnom par P 06 ref rpm s E 11 Decel Time 2 Range Function 20 00 s 1 00 3600 s Enter the decel time that is the deceleration time from parameter P 06 Base Speed 0 RPM Select a decel time such that no overvoltage arises in the inverter due to regenerative operation of the motor and such that the generated cur...

Page 47: ...the output is set in parameter E 90 Digital Relay Bus Control The output state is retained in the event of bus time out 46 Bus ctrl 1 if timeout Controls output via bus The state of the output is set in parameter E 90 Digital Relay Bus Control In the event of bus time out the output state is set high On 47 Bus ctrl 0 if timeout Controls output via bus The state of the output is set in parameter E ...

Page 48: ...ock function has been reset to default 2000 01 01 because of a power failure 181 Prev Maintenance One or more of the Preventive Maintenance Events programmed in parameter T 10 Maintenance Item has passed the time for the specified action in parameter T 11 Maintenance Action 190 No Flow A No Flow situation or Minimum Speed situation has been detected if enabled in parameter AP 21 Low Power Detectio...

Page 49: ...3 7 E 20 Terminal 27 Digital Output Option Function Same options and functions as parameter group E 2 E 21 Terminal 29 Digital Output Option Function Same options and functions as parameter group E 2 E 24 Function Relay Array 8 Relay 1 0 Relay 2 1 Option OPCRLY Relay 7 6 Relay 8 7 and Relay 9 8 Option Function Same options and functions as parameter group E 2 E 26 On Delay Relay Array 20 Range Fun...

Page 50: ... parameter is active when the General Purpose I O Option Module is mounted in the frequency converter Option Function Same options and functions as parameter group E 2 3 3 4 E 6 Pulse Input E 60 Term 29 Low Frequency Range Function 100 Hz 0 110000 Hz Enter the low frequency limit corresponding to the low motor shaft speed that is low reference value in parameter E 62 Term 29 Low Ref Feedb Value Re...

Page 51: ...7 Pulse Output E 70 Terminal 27 Pulse Output Variable Option Function 0 No operation 45 Bus ctrl 48 Bus ctrl timeout 100 Output frequency 101 Reference E 70 Terminal 27 Pulse Output Variable Option Function 102 Feedback 103 Motor Current 104 Torque rel to limit 105 Torq relate to rated 106 Power 107 Speed 113 Ext Closed Loop 1 114 Ext Closed Loop 2 115 Ext Closed Loop 3 E 71 Pulse Output Max Freq ...

Page 52: ...ut Terminal 27 Bit 1 CC Digital Output Terminal 29 Bit 2 GPIO Digital Output Terminal X 30 6 Bit 3 GPIO Digital Output Terminal X 30 7 Bit 4 CC Relay 1 output terminal Bit 5 CC Relay 2 output terminal Bit 6 Option B Relay 1 output terminal Bit 7 Option B Relay 2 output terminal Bit 8 Option B Relay 3 output terminal Bit 9 31 Reserved for future terminals Table 3 8 E 93 Pulse Out 27 Bus Control Ran...

Page 53: ...set Range Function 0 0 100 Contains the frequency to apply to the digital output terminal X30 6 when it is configured as bus controlled timeout and timeout is detected Parameter Description 52 03 2016 All rights reserved DET 620D 3 3 ...

Page 54: ...problems in the system Enter the upper limits of the speeds to be avoided C 04 Jump Frequency To Hz Array 4 Range Function 0 Hz 0 par F 15 Hz Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system Enter the upper limits of the speeds to be avoided C 05 Multi step Frequency 1 8 Array 8 Range Function 0 100 100 Enter up to 8 different prese...

Page 55: ...mit is defined in parameter F 17 Motor Speed High Limit RPM C 21 Jog Speed RPM Range Function See also parameter C 20 Jog Speed Hz and parameter C 22 Jog Accel Decel Time C 22 Jog Accel Decel Time Range Function 20 00 s 1 3600 s Enter the jog ramp time that is the acceleration deceleration time between 0 RPM and the nominal motor speed nM N set in parameter P 06 Base Speed Ensure that the resultin...

Page 56: ...se input 29 8 Pulse input 33 20 Digital Potenti ometer C 30 Frequency Command 2 Option Function 21 Analog input X30 11 OPCGPIO 22 Analog input X30 12 OPCGPIO 23 Analog Input X42 1 OPCAIO 24 Analog Input X42 3 OPCAIO 25 Analog Input X42 5 OPCAIO 30 Ext Closed Loop 1 31 Ext Closed Loop 2 32 Ext Closed Loop 3 C 34 Frequency Command 3 Option Function NOTICE This parameter cannot be adjusted while the ...

Page 57: ...Closed Loop 2 32 Ext Closed Loop 3 3 4 4 C 4 Semi Auto Jump Freq Set up C 40 Semi Auto Jump Freq Set up Option Function 0 Off No function 1 Enabled Starts the semi automatic bypass set up and continues with the procedure described in Parameter Description 56 03 2016 All rights reserved DET 620D 3 3 ...

Page 58: ...Rs in the system only Select this option if an LC filter is used between the frequency converter and the motor Activate the Auto Tune function by pressing Hand after selecting 1 Enable complete AMA or 2 Enable reduced AMA After a normal sequence the display reads Press OK to finish Auto Tune After pressing OK the frequency converter is ready for operation NOTICE For the best results of the frequen...

Page 59: ...tant Range Function 0 10 s 0 05 5 s NOTICE Parameter P 10 Slip Compensation Time Constant has no effect when parameter P 20 Motor Construction 1 PM non salient SPM Enter the slip compensation reaction speed A high value results in slow reaction and a low value results in quick reaction If low frequency resonance problems arise use a longer time setting P 20 Motor Construction Select the motor cons...

Page 60: ...basis of the motor nameplate data P 35 Main Reactance Xh Range Function 100 0000 Ohm 1 0000 10000 0000 Ohm NOTICE Parameter P 35 Main Reactance Xh does not have effect when parameter P 20 Motor Construction 1 PM non salient SPM Set the main reactance of the motor using 1 of these methods Run an Auto Tune on a cold motor The frequency converter measures the value from the motor Enter the Xh value m...

Page 61: ...and induction are shown in Illustration 3 21 GE frequency converters always require the line to common value The back EMF of a PM motor is defined as induced EMF developed across any of 2 phases of stator winding of a free running motor GE frequency converters always require the line to line RMS value measured at 1000 RPM mechanical speed of rotation This is shown in Illustration 3 22 Illustration...

Page 62: ...pplier provides an induction curve enter the induction value at 200 of the nominal value P 46 Position Detection Gain Range Function 100 20 200 Adjusts the amplitude of the test pulse during position detection at start Adjust this parameter to improve the position measurement P 47 Torque Calibration Option Function 0 Off 1 1st start after pwr up 2 Every start 3 1st start with store 4 Every start w...

Page 63: ...igital inputs 1 Automatic reset x 1 Select Automatic reset x 1 x20 1 12 to perform between one and twenty automatic resets after tripping H 04 Auto Reset Times Option Function 2 Automatic reset x 2 3 Automatic reset x 3 4 Automatic reset x 4 5 Automatic reset x 5 6 Automatic reset x 6 7 Automatic reset x 7 8 Automatic reset x 8 9 Automatic reset x 9 10 Automatic reset x 10 11 Automatic reset x 15 ...

Page 64: ...Parking Time Parameter B 03 DC Brake Cut In Speed RPM Parameter B 04 DC Brake Cut In Speed Hz Parameter B 06 Parking Current H 09 Start Mode Option Function Parameter B 07 Parking Time The flying start function used for PM motors is based on an initial speed estimation The speed is always estimated as the first thing after an active start signal is given Based on the setting of parameter F 20 PM S...

Page 65: ... H 43 Torque Characteristics Option Function 0 Compressor torque For speed control of screw and scroll compressors Provides a voltage which is optimised for a constant torque load charac teristic of the motor in the entire range down to 10 Hz 1 Variable torque For speed control of centrifugal pumps and fans Also to be used when controlling more than 1 motor from the same frequency converter for ex...

Page 66: ...Enter a value which is a percentage of the rated magnetizing current If the setting is too low the torque on the motor shaft may be reduced H 50 Motor Magnetisation at Zero Speed This parameter is not visible on the LCP Range Function Illustration 3 24 Motor Magnetisation H 51 Min Speed Normal Magnetising RPM This parameter is not visible on the LCP Range Function 15 RPM 10 300 RPM NOTICE Paramete...

Page 67: ...motor speed below which the parking function see parameter B 06 Parking Current and parameter B 07 Parking Time becomes active This parameter is only active when parameter F 20 PM Start Mode is set to 1 Parking and only after starting the motor 3 6 5 H 6 Load Depend Setting H 61 High Speed Load Compensation This parameter is not visible on the LCP Range Function 100 0 300 NOTICE Parameter H 61 Hig...

Page 68: ...ion 3600 RPM par H 72 60000 RPM NOTICE Any changes in parameter F 17 Motor Speed High Limit RPM reset the value in parameter H 73 Warning Speed High to the same value as set in parameter F 17 Motor Speed High Limit RPM If a different value is needed in parameter H 73 Warning Speed High it must be set after programming of parameter F 17 Motor Speed High Limit RPM Enter the nHIGH value When the moto...

Page 69: ...top command or after the speed is deceled to the settings in parameter H 81 Min Speed for Function at Stop RPM Available selections depend on parameter P 20 Motor Construction 0 Asynchronous 0 Coast 1 DC hold H 80 Function at Stop Option Function 2 Motor check warning 6 Motor check alarm 1 PM non salient 0 Coast 0 Coast Leaves motor in free mode 1 DC Hold Motor Preheat Energizes motor with a DC ho...

Page 70: ...e Zero Timeout Function is activated if the input signal on terminal 53 or 54 is below 50 of the value in Parameter AN 10 Terminal 53 Low Voltage Parameter AN 12 Terminal 53 Low Current Parameter AN 20 Terminal 54 Low Voltage AN 01 Live Zero Timeout Function Option Function Parameter AN 22 Terminal 54 Low Current The function can also be activated for a time period defined in parameter AN 00 Live ...

Page 71: ... to the high reference feedback set in parameter AN 15 Terminal 53 High Ref Feedb Value AN 14 Terminal 53 Low Ref Feedb Value Range Function 0 999999 999 999999 999 Enter the analog input scaling value that corresponds to the low voltage low current set in parameter AN 10 Terminal 53 Low Voltage and parameter AN 12 Terminal 53 Low Current AN 15 Terminal 53 High Ref Feedb Value Range Function 100 0...

Page 72: ...arameter AN 20 Terminal 54 Low Voltage and parameter AN 22 Terminal 54 Low Current AN 25 Terminal 54 High Ref Feedb Value Range Function 100 999999 999 999999 999 Enter the analog input scaling value that corresponds to the high voltage high current value set in parameter AN 21 Terminal 54 High Voltage and parameter AN 23 Terminal 54 High Current AN 26 Terminal 54 Filter Time Constant Range Functi...

Page 73: ...placed on General Purpose I O OPCGPIO General Purpose I O AN 40 Terminal X30 12 Low Voltage Range Function 0 07 V 0 par AN 41 V Sets the analog input scaling value to correspond to the low reference feedback value set in parameter AN 44 Term X30 12 Low Ref Feedb Value AN 41 Terminal X30 12 High Voltage Range Function 10 V par AN 40 10 V Sets the analog input scaling value to correspond to the high...

Page 74: ...rque Limiter Driving 0 20 mA 105 Torq relate to rated 0 Motor rated torque 0 20 mA 106 Power 0 Motor rated power 0 20 mA 107 Speed 0 Speed high limit parameter F 17 Motor Speed High Limit RPM and parameter F 15 Motor Speed High Limit Hz 0 20 mA 113 Ext Closed Loop 1 0 100 0 20 mA AN 50 Terminal 42 Output Option Function 114 Ext Closed Loop 2 0 100 0 20 mA 115 Ext Closed Loop 3 0 100 0 20 mA 117 Sh...

Page 75: ...d for output 0 100 Output signal 0 mA or 4 mA is needed at 0 50 of range Set parameter AN 51 Terminal 42 Output Min Scale to 50 Output signal 20 mA is needed at 100 75 of range Set parameter AN 52 Terminal 42 Output Max Scale to 75 Example 3 Variable value reference range minimum reference maximum reference Range needed for output minimum reference 0 maximum reference 100 0 10 mA Output signal 0 m...

Page 76: ...arameter AN 62 Terminal X30 8 Max Scale if the value is below 100 This parameter is active when General Purpose I O OPCGPIO General Purpose I O is mounted in the frequency converter AN 62 Terminal X30 8 Max Scale Range Function 100 0 200 Scales the maximum output of the selected analog signal on terminal X30 8 Scale the value to the required maximum value of the current signal output Scale the out...

Page 77: ... E 0 Only selections 0 No function 3 Coasting or 6 Alarm are available when parameter P 20 Motor Construction is set to 1 PM non salient SPM 0 No function The energy left in the capacitor bank is used to run the motor but is discharged 1 Ctrl Decel The frequency converter performs a controlled decel Parameter B 10 Brake Function must be set to 0 Off SP 10 Line failure Option Function 3 Coasting Th...

Page 78: ...miter Braking a warning is triggered When the torque limit warning has been continuously present for the period specified in this parameter the frequency converter trips Disable the trip delay by setting the parameter to 60 s OFF Thermal frequency converter monitoring remains active SP 26 Trip Delay at Drive Fault Range Function 1 s 0 35 s When the frequency converter detects an overvoltage in the...

Page 79: ...tor Construction is set to 1 PM non salient SPM SP 41 Energy Savings Min Magnetization Range Function Enter the minimum allowable magnetization for Automatic Energy Savings Selection of a low value reduces energy loss in the motor but can also reduce resistance to sudden load changes SP 42 Energy Savings Min Frequency Range Function 10 Hz 5 40 Hz NOTICE This parameter is not active when parameter ...

Page 80: ...he timer starts once the AHF capacitor disconnects and connects back once delay expires and frequency converters power above 20 and below 30 of nominal power AHF capacitor connect output function for digital and relay outputs Functional description 1 Connect capacitors at 20 nominal power 2 Hysteresis 50 of the 20 nominal power minimum 10 and maximum 30 nominal power 3 Off delay timer 10 s The nom...

Page 81: ...ent 0 Trip The frequency converter trips trip lock and generate an alarm Cycle power to reset the alarm The motor restarts when the heat sink temperature has dropped below the alarm limit 1 Derate If the critical temperature is exceeded the output current is reduced until the allowable temperature has been reached SP 61 Function at Drive Overload Option Function Is used in case of steady overload ...

Page 82: ...O 30 0 Drive 1 Drive MC 2 Modbus RTU 3 Metasys N2 or 4 FLN 0 None 1 Drive Port The drive port is the RS485 port running the protocol as set in parameter O 30 Drive Drive MC Modbus RTU Metasys N2 or FLN 2 USB Port 3 Option A 4 Option B 30 External Can O 03 Control Word Timeout Time Range Function 60 0 s 0 5 18000 s Enter the maximum time expected to pass between the reception of 2 consecutive messa...

Page 83: ...l fieldbusses support the diagnosis functions 0 Disable 1 Trigger on alarms 2 Trigger alarm warn O 08 Readout Filtering If the speed feedback value readouts on fieldbus are fluctuating this function is used Select filtered if the function is required A power cycle is required for changes to take effect Option Function 0 Motor Data Std Filt Normal fieldbus readouts 1 Motor Data LP Filter Filtered f...

Page 84: ...y 16 Option Function 65 Comparator 5 See parameter group LC 1 Comparators If comparator 5 is evaluated as TRUE the output goes high Otherwise it is low 70 Logic Rule 0 See parameter group LC 4 Logic Rules If logic rule 0 is evaluated as TRUE the output goes high Otherwise it is low 71 Logic Rule 1 See parameter group LC 4 Logic Rules If logic rule 1 is evaluated as TRUE the output goes high Otherw...

Page 85: ...n the drive and their inter depend encies to DCT 10 O 30 Protocol Option Function 2 Modbus RTU Communication according to the Modbus RTU protocol as described in the AF 600 FP AF 600 FP Design Guide RS485 Installation and Set up 3 Metasys N2 Communication according to the Metasys N2 protocal 4 FLN Communication according to the Apogee FLN P1 protocol 9 Drive Option To be used when a gateway is con...

Page 86: ...r standard messages for the Drive port 1 Standard telegram 1 101 PPO 1 102 PPO 2 103 PPO 3 104 PPO 4 O 40 Telegram Selection Option Function 105 PPO 5 106 PPO 6 107 PPO 7 108 PPO 8 200 Custom telegram 1 O 42 PCD Write Configuration Option Function 0 None Select the parameters to be assigned to PCD s messages The number of available PCDs depends on the message type The values in PCD s will then be ...

Page 87: ... Feedback Unit 1253 Digi Pot Reference 1254 Feedback 1 Unit 1255 Feedback 2 Unit 1256 Feedback 3 Unit 1260 Digital Input O 43 PCD Read Configuration Option Function 1261 Terminal 53 Switch Setting 1262 Analog Input 53 1263 Terminal 54 Switch Setting 1264 Analog Input 54 1265 Analog Output 42 mA 1266 Digital Output bin 1267 Freq Input 29 Hz 1268 Freq Input 33 Hz 1269 Pulse Output 27 Hz 1270 Pulse O...

Page 88: ...art function O 54 Reversing Select Option Function NOTICE This parameter is active only when parameter O 01 Control Site is set to 0 Digital and control word O 54 Reversing Select Option Function Select control of the drive reverse function via the terminals digital input and or via the fieldbus 0 Digital input Activates reverse command via a digital input 1 Bus Activates reverse command via the s...

Page 89: ...7483648 2147483647 3 9 7 O 9 Bus Jog Feedback O 90 Bus Jog 1 Speed Range Function 100 RPM 0 par F 17 RPM Enter the jog speed Activate this fixed jog speed via the serial port or network option O 91 Bus Jog 2 Speed Range Function 200 RPM 0 par F 17 RPM Enter the jog speed Activate this fixed jog speed via the serial port or network option O 94 Bus Feedback 1 Range Function 0 200 200 Write feedback ...

Page 90: ...0 C if operating in Celsius or 3 Pt 1000 F and 5 Ni 1000 F if operating in Fahrenheit NOTICE If the input is not in use set it for voltage If set for temperature and used as feedback set the unit for either Celsius or Fahrenheit AO 01 Terminal X42 3 Mode Option Function Parameter CL 12 Reference Feedback Unit Parameter XC 10 Ext 1 Ref Feedback Unit Parameter XC 30 Ext 2 Ref Feedback Unit Parameter...

Page 91: ... as a building management system 0 Disabled 1 Enabled 3 10 3 AO 2 Analog Input X42 3 AO 20 Terminal X42 3 Low Voltage Range Function 0 07 V 0 par AN 31 V Enter the low voltage value This analog input scaling value should correspond to the low reference feedback value set in parameter AO 24 Term X42 3 Low Ref Feedb Value AO 21 Terminal X42 3 High Voltage Range Function 10 V par AN 30 10 V Enter the...

Page 92: ...ve Zero Option Function Enable or disable the live zero monitoring 0 Disabled 1 Enabled 3 10 5 AO 4 Analog Out X42 7 AO 40 Terminal X42 7 Output Option Function Set the function of terminal X42 7 as an analog current output 0 No operation 100 Output frequency 0 100 Hz 0 10 V 101 Reference Minimum reference maximum reference 0 10 V 102 Feedback 200 to 200 of parameter F 53 Maximum Reference 0 10 V ...

Page 93: ...05 Torq relate to rated 0 motor rated torque 0 10 V AO 50 Terminal X42 9 Output Option Function 106 Power 0 motor rated power 0 10 V 107 Speed 0 speed high limit parameter F 17 Motor Speed High Limit RPM and parameter F 15 Motor Speed High Limit Hz 0 10 V 113 Ext Closed Loop 1 0 100 0 10 V 114 Ext Closed Loop 2 0 100 0 10 V 115 Ext Closed Loop 3 0 100 0 10 V 139 Bus ctrl 0 100 0 10 V 141 Bus ctrl ...

Page 94: ...nal at terminal X42 11 as a percentage of the maximum signal level For example if 0 V is required at 25 of the maximum output value program 25 Scaling values up to 100 can never be higher than AO 61 Terminal X42 11 Min Scale For more information see parameter AN 51 Terminal 42 Output Min Scale Range Function the corresponding setting in parameter AO 62 Terminal X42 11 Max Scale AO 62 Terminal X42 ...

Page 95: ...he instance message for data transmission The instances available depend on the setting of parameter O 10 Control Word Profile When parameter O 10 Control Word Profile is set to 0 Drive protocol parameter DN 10 Process Data Type Selection options 0 INSTANCE 100 150 and 1 INSTANCE 101 151 are available When parameter O 10 Control Word Profile is set to 5 ODVA parameter DN 10 Process Data Type Selec...

Page 96: ...r Resistance 1230 DC Link Voltage 1232 Brake Energy s 1233 Brake Energy Average 1234 Heatsink Temp DN 12 Process Data Config Read Option Function 1235 Drive Thermal 1238 Logic Controller State 1239 Control Card Temp 1250 External Reference 1252 Feedback Unit 1253 Digi Pot Reference 1254 Feedback 1 Unit 1255 Feedback 2 Unit 1256 Feedback 3 Unit 1260 Digital Input 1261 Terminal 53 Switch Setting 126...

Page 97: ...OS Filter 1 Range Function 0 0 65535 Enter the value for COS filter 1 to set up the filter mask for the status word When operating in COS change of state this function filters out bits in the status word that should not be sent if they change DN 21 COS Filter 2 Range Function 0 0 65535 Enter the value for COS filter 2 to set up the filter mask for the Main Actual Value When operating in COS this f...

Page 98: ...all set ups in the non volatile memory The selection returns to 0 Off when all parameter values have been stored DN 32 Devicenet Revision Range Function 0 0 65535 View the DeviceNet revision number This parameter is used for EDS file creation DN 33 Store Always Option Function 0 Off Deactivates non volatile storage of data 1 On Stores parameter data received via DeviceNet MCA 104 in EEPROM non vol...

Page 99: ...TW 1 1286 Drive Port REF 1 PB 16 PCD Read Configuration Option Function Select the parameters to be assigned to PCD 3 to 10 of the messages The number of available PCDs depends on the telegram type PCDs 3 to 10 contain the actual data values of the selected parameters For standard Profibus message see parameter PB 22 Telegram Selection 0 None 515 Readout Actual Set up 894 Bus Feedback 1 895 Bus Fe...

Page 100: ...ction Option Function 101 PPO 1 102 PPO 2 103 PPO 3 104 PPO 4 105 PPO 5 106 PPO 6 107 PPO 7 108 PPO 8 PB 23 Parameters for Signals Array 1000 Option Function This parameter contains a list of signals available for selection in parameter PB 15 PCD Write Configuration and parameter PB 16 PCD Read Configuration PB 27 Parameter Edit Option Function Edit parameters via PROFIBUS The standard RS485 inter...

Page 101: ... 14 Timeout active 15 Warning 34 Fieldbus fault active Table 3 14 PROFIBUS Warning Word PB 63 Actual Baud Rate Option Function This parameter shows the actual PROFIBUS baud rate The PROFIBUS master automatically sets the baud rate 0 9 6 kbit s 1 19 2 kbit s PB 63 Actual Baud Rate Option Function 2 93 75 kbit s 3 187 5 kbit s 4 500 kbit s 6 1500 kbit s 7 3000 kbit s 8 6000 kbit s 9 12000 kbit s 10 ...

Page 102: ...e Function 0 0 65535 Provides information about the DO Drive Object PB 80 Defined Parameters 1 Array 116 No keypad access Read only Range Function 0 0 9999 This parameter shows a list of all the defined frequency converter parameters available for PROFIBUS PB 81 Defined Parameters 2 Array 116 No keypad access Read only Range Function 0 0 9999 This parameter shows a list of all the defined frequenc...

Page 103: ...0 9999 This parameter shows a list of all the frequency converter parameters deviating from default setting PB 93 Changed Parameters 4 Range Function 0 0 9999 PB 94 Changed Parameters 5 Array 116 No keypad Address Read only Range Function 0 0 9999 This parameter shows a list of all the frequency converter parameters deviating from default setting PB 99 Profibus Revision Counter Range Function 0 0 ...

Page 104: ...rvers Range Function 0 0 2147483647 IP addresses of domain name servers Can be automatically assigned when using DHCP EN 07 Domain Name Range Function 0 0 48 Domain name of the attached network Can be automatically assigned when using DHCP network EN 08 Host Name Range Function Blank 0 19 characters Logical given name of option EN 09 Physical Address Range Function 0 0 17 Read only Shows the physi...

Page 105: ... The parameter returns to 0 Off 0 Off The store function is inactive 1 Store All set ups All parameter values are stored in the non volatile memory in all 5 set ups EN 29 Store Always Option Function Activates function that always stores received parameter data in non volatile memory EEPROM 0 Off 1 On EN 30 Warning parameter Range Function 0000 FFFF hex Read only Displays the Ethernet IP specific ...

Page 106: ...fault value is 4000 0 means disabled EN 90 Cable Diagnostic Option Function NOTICE The cable diagnostics function is only issued on ports where there is no link see parameter EN 10 Link Status Link Status Enables disables advanced cable diagnosis function If enabled the distance to cable errors can be read out in parameter EN 93 Cable Error Length The parameter resumes to the default setting of di...

Page 107: ...m protection should also include multicast messages 0 Broadcast only 1 Broadcast Multicast EN 96 Port Mirroring Enables disables port mirroring function For troubleshooting with a network analyzer tool Option Function 0 Disable No port mirroring 1 Port 1 to Port 2 All network traffic on port 1 is mirrored to port 2 2 Port 2 to Port 1 All network traffic on port 2 is mirrored to port 1 10 Port 1 di...

Page 108: ... this network Decreasing this value optimises polling for the token BN 73 MS TP Max Info Frames Range Function 1 1 65534 Define how many info data frames the device is allowed to send while holding the token BN 74 I Am Service Option Function 0 Send at power up 1 Continuously Select whether the device should send the I Am service message only at power up or continuously with an interval of approx ...

Page 109: ...itialisation error 11 Internal communication error 12 Software revision mismatch 13 Bus not active 14 Option not present 15 LON input nvi nci exceeds limits Table 3 16 LON Warning Word LN 17 XIF Revision Range Function 0 0 5 This parameter contains the version of the external interface file on the Neuron C chip on the LON option LN 18 LonWorks Revision Range Function 0 0 5 This parameter contains ...

Page 110: ...Wh Counter ID 07 Reset Running Hours Counter Option Function 0 Do not reset No reset of the running hours counter is required 1 Reset counter Select 1 Reset counter and press OK to reset the running hours counter parameter ID 01 Running Hours and parameter ID 08 Number of Starts to 0 see also parameter ID 01 Running Hours ID 08 Number of Starts Range Function 0 0 2147483647 NOTICE This parameter i...

Page 111: ...s applied to freeze the log The log then retains a specified percentage of samples before the occurrence of the trigger event parameter ID 14 Samples Before Trigger ID 12 Trigger Event Option Function 0 False 1 True 2 Running 3 In range 4 On reference 5 Torque limit 6 Current Limit 7 Out of current range 8 Below I low 9 Above I high 10 Out of speed range 11 Below speed low 12 Above speed high 13 O...

Page 112: ...mal value See parameter DR 60 Digital Input for description after converting to binary value ID 21 Historic Log Value Array 50 Range Function Digital output Decimal value See parameter DR 66 Digital Output bin for a description after converting to binary value Warning word Decimal value See parameter DR 92 Warning Word for a description Alarm word Decimal value See parameter DR 90 Alarm Word for a...

Page 113: ...0 0 20 View the Drive type ID 43 Software Version Range Function 0 0 5 View the SW version ID 44 GE Model Number Range Function 0 0 40 View the model number string used for reordering the frequency converter in its original configu ration ID 45 Actual Typecode String Range Function 0 0 40 View the actual type code string ID 46 GE Product No Range Function 0 0 8 View the 8 digit number To restore t...

Page 114: ...ction 0 0 30 View the type code string for the option installed in slot C and a translation of the type code string For example for type code string CXXXX the translation is No option ID 75 Slot C0 Option SW Version Range Function 0 0 20 View the software version for the option installed in slot C ID 76 Option in Slot C2 Range Function 0 0 30 Shows the typecode string for the options CXXXX if no o...

Page 115: ...Identification Range Function 0 0 40 ID 99 Parameter Metadata Array 30 Range Function 0 0 9999 This parameter contains data used by the DCT 10 tool Parameter Description 114 03 2016 All rights reserved DET 620D 3 3 ...

Page 116: ...0 kW 0 10000 kW Shows motor power in kW The value shown is calculated based on the actual motor voltage and motor current The value is filtered and therefore approximately 1 3 s may pass from when an input value changes to when the data readout values change The resolution of readout value on fieldbus is in 10 W steps DR 11 Power hp Range Function 0 hp 0 10000 hp View the motor power in hp The val...

Page 117: ...aft torque and motor speed DR 24 Calibrated Stator Resistance Range Function 0 0000 Ohm 0 0000 100 0000 Ohm 3 17 3 DR 3 Drive Status DR 30 DC Link Voltage Range Function 0 V 0 10000 V View a measured value The value is filtered with a 30 ms time constant DR 31 System Temp Range Function 0 C 128 127 C DR 32 Brake Energy s Range Function 0 kW 0 10000 kW View the brake power transmitted to an externa...

Page 118: ...r cycle but if a new alarm occurs it is overwritten by the new power card number even if it is a lower priority number The value is only cleared when the alarm log is cleared that is a 3 finger reset would reset the readout to 0 3 17 4 DR 5 Ref Feedb DR 50 External Reference Range Function 0 200 200 View the total reference the sum of digital analog preset fieldbus and freeze references plus catch...

Page 119: ...ange Function 0 0 1023 View the signal states from the active digital inputs Example Input 18 corresponds to bit number 5 0 no signal 1 connected signal DR 60 Digital Input Range Function Bit 0 Digital input terminal 33 Bit 1 Digital input terminal 32 Bit 2 Digital input terminal 29 Bit 3 Digital input terminal 27 Bit 4 Digital input terminal 19 Bit 5 Digital input terminal 18 Bit 6 Digital input ...

Page 120: ...n 0 2147483648 2147483647 View the present value of counter B Counters are useful as comparator operands parameter LC 10 Comparator Operand Reset or change the value either via digital inputs parameter group E 0 or by using an LC action parameter LC 52 Logic Controller Action DR 75 Analog In X30 11 Range Function 0 20 20 View the actual value at input X30 11 of General Purpose I O OPCGPIO General ...

Page 121: ...he warning word sent via the serial communication port in hex code DR 93 Warning Word 2 Range Function 0 0 4294967295 View the warning word 2 sent via the serial communication port in hex code DR 94 Ext Status Word Range Function 0 0 4294967295 Returns the extended status word sent via the serial communication port in hex code DR 95 Ext Status Word 2 Range Function 0 0 4294967295 Returns the exten...

Page 122: ...ce Word Example The preventive maintenance word shows 040Ahex Position 1 2 3 4 Hex value 0 4 0 A Table 3 20 Example The first digit 0 indicates that no items from the 4th row require maintenance The 2nd digit 4 refers to the 3rd row indicating that the frequency converter cooling fan requires maintenance The 3rd digit 0 indicates that no items from the 2nd row require maintenance The 4th digit A r...

Page 123: ... on the setting in parameter K 72 Time Format LG 03 Maintenance Log Date and Time Array 10 Range Function NOTICE The frequency converter has no back up of the clock function and the set date time resets to default 2000 01 01 00 00 after a power down unless an Analog I O Option Module with Real Time Clock Battery Back Up OPCAIO is installed In parameter K 79 Clock Fault it is possible to program a ...

Page 124: ...l X42 3 on the analog I O card The units of the value shown in the keypad correspond to the mode selected in parameter AO 01 Terminal X42 3 Mode LG 32 Analog Input X42 5 Range Function 0 20 20 Readout of the value of the signal applied to terminal X42 5 on the analog I O card The units of the value shown in the keypad correspond to the mode selected in parameter AO 02 Terminal X42 5 Mode LG 33 Ana...

Page 125: ...ogrammed for external interlock before reaction takes place 3 19 1 AP 2 No Flow Detection Illustration 3 39 No flow Detection The frequency converter includes functions for detecting if the load conditions in the system allow the motor to be stopped Low power detection Low speed detection One of these 2 signals must be active for a set time parameter AP 24 No Flow Delay before selected action take...

Page 126: ...nd associated power at no flow Monitoring power enables detection of no flow conditions in systems with fluctuating suction pressure or of the pump having a flat characteristic towards low speed The 2 sets of data must be based on measurement of power at approximately 50 and 85 of maximum speed with the valves closed The data is programmed in parameter group AP 3 It is also possible to run a 0 Low...

Page 127: ...ct parameter AP 26 Dry Pump Function Warning Alarm Enable and commission no flow detection in parameter AP 23 No Flow Function and parameter group AP 3 No Power Tuning AP 20 Low Power Auto Set up Start of auto set up of power data for no flow power tuning Option Function 0 Off 1 Enabled NOTICE Do the auto set up when the system has reached normal operating temperature NOTICE It is important that p...

Page 128: ...ment 3 Alarm The frequency converter stops running and activates a no flow alarm alarm 92 NoFlow A frequency converter digital output or a serial AP 23 No Flow Function Common actions for low power detection and low speed detection individual selections not possible Option Function communication bus can communicate an alarm to other equipment AP 24 No Flow Delay Range Function 10 s 1 600 s Set the...

Page 129: ...oximately 50 of rated speed Note the exact speed 6 Read power consumption either by looking for actual power in the data line in the keypad or by viewing 1 of the following parameters 6a Parameter DR 10 Power kW or 6b Parameter DR 11 Power hp in the Main Menu Note the power readout 7 Program the speeds used in 7a Parameter AP 32 Low Speed RPM 7b Parameter AP 33 Low Speed Hz 7c Parameter AP 36 High...

Page 130: ... Power HP Range Function 0 hp 0 7 50 hp To be used if parameter K 03 Regional Settings is set for 1 North America parameter not visible if 0 International is selected Set power consumption at 85 speed level This function is used for storing values necessary for tuning no flow detection 3 19 3 AP 4 Sleep Mode If the load on the system allows for stop of the motor and the load is monitored the motor...

Page 131: ...s the setpoint for pressure to ensure a slight overpressure in the system boost to be set in parameter AP 45 Setpoint Boost The feedback from the pressure transducer is monitored and when this pressure has dropped with a set percentage below the normal setpoint for pressure Pset the motor acccel again and the pressure reaches the set value Pset Illustration 3 42 Boost System 2 In systems where the...

Page 132: ... has been set for 0 RPM parameter not visible if 1 Hz is selected Only to be used if parameter H 40 Configuration Mode is set for 0 Open loop and an external controller applies speed reference Set the reference speed at which the sleep mode should be canceled AP 43 Wake up Speed Hz Range Function 0 Hz par F 16 To be used if parameter K 02 Motor Speed Unit has been set for 1 Hz parameter not visibl...

Page 133: ...r AP 50 End of Curve Function is set to 2 Alarm Doing so causes the frequency converter to continuously cycle between running and stopping when an end of curve condition is detected AP 50 End of Curve Function Option Function NOTICE If the frequency converter is equipped with a constant speed bypass with an automatic bypass function that starts the bypass if the frequency converter experiences a p...

Page 134: ...by the minimum run time function parameter AP 77 Minimum Run Time and any normal start command start jog freeze can be overridden by the interval between starts function parameter AP 76 Interval between Starts None of the 2 functions are active if hand on or off modes have been activated via the keypad If selecting hand on or off the 2 timers are reset to 0 and not start counting until Auto is pre...

Page 135: ...hen parameter P 20 Motor Construction 1 PM non salient SPM The time from the start signal is given until the speed exceeds the speed set in parameter AP 70 Compressor Start Max Speed RPM must not exceed the time set in the parameter If the time set is exceeded the frequency converter trips with alarm 18 Start failed AP 72 Compressor Start Max Time to Trip Range Function Any time set in parameter F...

Page 136: ... Parameter AP 84 Speed at No Flow Hz Parameter AP 85 Speed at Design Point RPM Parameter AP 86 Speed at Design Point Hz parameter AP 87 Pressure at No Flow Speed Parameter AP 88 Pressure at Rated Speed Parameter AP 89 Flow at Design Point Parameter AP 90 Flow at Rated Speed Table 3 23 Number of Pumps AP 80 Flow Compensation Option Function 0 Disabled Setpoint compensation not active 1 Enabled Setp...

Page 137: ...k Point Calculation Option Function Illustration 3 48 Speed at System Design Working Point is not Known 0 Disabled Work point calculation not active To be used if speed at design point is known 1 Enabled Work point calculation is active Enabling this parameter allows the calculation of the unknown system design working point at 50 60 Hz speed from the input data set in Parameter AP 83 Speed at No ...

Page 138: ...een decided to use Hz in parameter K 02 Motor Speed Unit parameter AP 83 Speed at No Flow RPM should also be used AP 87 Pressure at No Flow Speed Range Function 0 0 par AP 88 Enter the pressure HMIN corresponding to speed at no flow in reference feedback units AP 88 Pressure at Rated Speed Also see parameter AP 82 Work Point Calculation Range Function 999999 999 par AP 87 999999 999 Enter the valu...

Page 139: ...interruption Activation Fire mode is activated only via digital Input terminals See parameter group E 0 Digital Inputs Messages in display When fire mode is activated the display shows a status message Fire Mode and a warning Fire Mode Once the fire mode is again deactivated the status messages disappears and the warning is replaced by the warning Fire M Was Active This message can only be reset b...

Page 140: ...lockwise direction Works only in open loop Set parameter FB 01 Fire Mode Configuration to 0 Open Loop 3 Enabled Coast In this mode the output is disabled and the motor is allowed to coast to stop 4 Enabled Run Fwd Rev FB 01 Fire Mode Configuration Option Function NOTICE Before adjusting the PID controller set parameter FB 09 Fire Mode Alarm Handling 2 Trip All Alarms Test NOTICE If 2 Enable Run Re...

Page 141: ...m of value in parameter FB 05 Fire Mode Preset Reference and value of signal on input selected in parameter FB 06 Fire Mode Reference Source If running in open loop when fire mode is active the unit is selected by the setting parameter K 02 Motor Speed Unit For closed loop select the unit in parameter FB 02 Fire Mode Unit FB 05 Fire Mode Preset Reference Range Function 0 100 100 Enter the required...

Page 142: ...n parameter H 04 Auto Reset Times is disregarded if fire mode is active see parameter group FB 0 Fire Mode Num ber Description Critical alarms Warranty affecting alarms 4 Mains oh Loss x 7 DC overvolt x 8 DC undervolt x 9 Inverter overloaded x 13 Over current x 14 Earth fault x 16 Short circuit x 29 Power card temp x 33 Inrush fault x 38 Internal fault x 65 Ctrl card temp x Table 3 25 Fire Mode Al...

Page 143: ...art attempts the timer continues to run while the frequency converter tries to restart Should the motor have restarted within the time period of the bypass delay timer the timer is reset FB 11 Drive Bypass Delay Time Range Function Should the motor fail to restart at the end of the bypass delay time the frequency converter bypass relay is activated which has been programmed for bypass in parameter...

Page 144: ... digital inputs or the logic controller NOTICE Programme the clock parameter group K 7 correctly for timed actions to function NOTICE When mounting Analog I O Option OPCAIO a battery back up of the date and time is included T 00 ON Time Array 10 Range Function 0 0 0 Sets the ON time for the timed action NOTICE The frequency converter has no back up of the clock function and the set date time reset...

Page 145: ...eset ref 0 11 Select preset ref 1 12 Select preset ref 2 13 Select preset ref 3 14 Select preset ref 4 15 Select preset ref 5 16 Select preset ref 6 17 Select preset ref 7 18 Select Accel Decel 1 19 Select Accel Decel 2 22 Run T 03 OFF Action Array 10 Option Function 23 Run reverse 24 Stop 26 DC Brake 27 Coast 32 Set digital out A low 33 Set digital out B low 34 Set digital out C low 35 Set digita...

Page 146: ...o see an example of a reactivation test see Illustration 3 50 Illustration 3 50 Reactivation Test Diagram 3 21 2 T 1 Maintenance Wear and tear calls for periodic inspection and service of elements in the application for example motor bearings feedback sensors and seals or filters With preventive maintenance the service intervals may be programmed into the frequency converter The frequency converte...

Page 147: ... selecting maintenance log NOTICE The preventive maintenance events are defined in a 20 element array Hence each preventive maintenance event must use the same array element index in parameter T 10 Maintenance Item to parameter T 14 Maintenance Date and Time T 10 Maintenance Item Array 20 Option Function Array with 20 elements showed below parameter number in the display Press OK and step between ...

Page 148: ... 1 2147483647 h Set the interval associated with the current preventive maintenance event This parameter is only used if 1 Running Hours or 2 Operating Hours is selected in parameter T 12 Maintenance Time Base The timer is reset from parameter T 15 Reset Maintenance Word Example A preventive maintenance event is set up Monday at 8 00 Parameter T 12 Maintenance Time Base is 2 Operating hours and pa...

Page 149: ...start Data related to a predefined period back in time for example last 7 days within the pre programmed period For each of the above 2 functions the data are stored in a number of counters allowing for selecting time frame and a split on hours days or weeks The period split resolution can be set in parameter T 50 Energy Log Resolution The data is based on the value registered by the kWh counter i...

Page 150: ...ting hours time where frequency converter is powered up 0 Hour of Day 1 Day of Week 2 Day of Month 5 Last 24 Hours 6 Last 7 Days 7 Last 5 Weeks T 51 Period Start Range Function 0 0 0 NOTICE When mounting Analog I O option a battery back up of the date and time is included Set the date and time at which the energy log starts updating the counters First data are stored in counter 00 and start at the...

Page 151: ...ividually but is 10 for each for default Power and current can exceed rated value but those registrations are included in 90 100 MAX counter Illustration 3 54 Time and Relative Values Once a second the value of the operating variable selected is registered If a value has been registered to equal 13 the counter 10 20 is updated with the value 1 If the value stays at 13 for 10 s 10 is added to the c...

Page 152: ...clock function and the set date time is reset to default 2000 01 01 00 00 after a power down unless the Analog I O option module OPCAIO with Battery Back Up of the Real Time Clock is installed Consequently the logging is stopped until date time is readjusted in parameter K 70 Date and Time In parameter K 79 Clock Fault it is possible to programme a warning if in case the clock has not been set pro...

Page 153: ...t in representing the power produced at fixed speed The difference between this reference power and the actual power is accumulated and stored The difference in energy can be read in parameter T 83 Energy Savings The accumulated value for the difference in power consumption is multiplied with the energy cost in local currency and the investment is subtracted This calculation for cost savings can a...

Page 154: ... period T 82 Investment Range Function 0 0 999999999 Set the value of the investment spent on upgrading the plant with speed control in same currency as used in parameter T 81 Energy Cost T 83 Energy Savings Range Function 0 kWh 0 0 kWh This parameter allows a readout of the accumulated difference between the reference power and the actual output power If motor size is set in hp parameter P 02 Mot...

Page 155: ...nction NOTICE If feedback is not used set its source to 0 No Function Parameter CL 20 Feedback Function determines how the PID controller uses the 3 possible feedbacks Up to 3 different feedback signals can be used to provide the feedback signal for the frequency converter s PID controller This parameter defines which input is used as the source of the first feedback signal Analog input X30 11 and...

Page 156: ...y Factor See also parameter CL 34 Duct 1 Area m2 through parameter CL 38 Air Density Factor for setting of duct area and air density 4 Velocity to flow Used in applications for controlling the air flow in a duct An air velocity measurement represents the feedback signal Flow Duct Area Air Velocity See also parameter CL 34 Duct 1 Area m2 through parameter CL 37 Duct 2 Area in2 for setting of duct a...

Page 157: ...Option Function 3 Pulse input 29 4 Pulse input 33 7 Analog Input X30 11 8 Analog Input X30 12 9 Analog Input X42 1 10 Analog Input X42 3 11 Analog Input X42 5 100 Bus Feedback 1 101 Bus Feedback 2 102 Bus feedback 3 CL 07 Feedback 3 Conversion Option Function See parameter CL 01 Feedback 1 Conversion for details 0 Linear 1 Square root 2 Pressure to temperature 3 Pressure to flow 4 Velocity to flow...

Page 158: ...ks are used to control the output frequency of the frequency converter 0 Sum Sets up the PID controller to use the sum of feedback 1 feedback 2 and feedback 3 as the feedback NOTICE Set any unused feedbacks to 0 No Function in Parameter CL 00 Feedback 1 Source Parameter CL 03 Feedback 2 Source Parameter CL 06 Feedback 3 Source The sum of setpoint 1 and any other references that are enabled see C 3...

Page 159: ...ference between the 2 CL 20 Feedback Function Option Function NOTICE If only 2 feedback signals are used set the non used feedback to 0 No Function in Parameter CL 00 Feedback 1 Source Parameter CL 03 Feedback 2 Source Parameter CL 06 Feedback 3 Source Note that each setpoint reference is the sum of its respective parameter value parameter CL 21 Setpoint 1 parameter CL 22 Setpoint 2 and parameter ...

Page 160: ...each duct the pressure at each VAV box cannot be assumed to be the same The minimum pressure required is the same for all VAV boxes This control method can be set up by setting parameter CL 20 Feedback Function to 3 Minimum and entering the desired pressure in parameter CL 21 Setpoint 1 If any feedback is below the setpoint the PID controller increases the fan speed If all feedbacks are above the ...

Page 161: ...point 3 Range Function NOTICE The setpoint reference entered here is added to any other references that are enabled see parameter F 01 Frequency Setting 1 parameter C 30 Frequency Command 2 and parameter C 34 Frequency Command 3 3 22 3 CL 3 Feedback Adv Conversion In air conditioning compressor applications it is often useful to control the system based on the temperature of the refrigerant Howeve...

Page 162: ...unction Fan 2 is used with feedback 2 In case of flow difference control set parameter CL 20 Feedback Function to 1 Difference if flow fan 1 flow fan 2 is to be controlled CL 38 Air Density Factor Range Function 100 50 150 Set the air density factor for conversion from pressure to flow in relative to the air density at sea level at 20 C 100 1 2 kg m3 3 22 4 CL 7 PID Auto Tuning The frequency conve...

Page 163: ...High Limit RPM parameter F 15 Motor Speed High Limit Hz is set to 50 Hz 0 10 is 10 of 50 Hz which is 5 Hz Set this parameter to a value resulting in feedback changes of 10 20 for best tuning accuracy CL 73 Minimum Feedback Level Range Function 999999 ProcessCtrlUnit 999999 999 par CL 74 ProcessCtrlUnit Enter the minimum allowable feedback level in user units as defined in parameter CL 12 Reference...

Page 164: ... status bit of the frequency converter status word is high value 1 The On Reference Bandwidth is calculated as a percentage of the setpoint reference 3 22 6 CL 9 PID Controller This group provides the ability to manually adjust the PID controller By adjusting the PID controller parameters the control performance may be improved See the AF 600 FP AF 600 FP Design Guide for guidelines on adjusting t...

Page 165: ...ickly it adjusts the output of the PID Controller to reduce the rate of change of the feedback Quick PID Controller response is obtained when this value is large However if too large of a value is used the frequency converter s output frequency may become unstable Differentiation time is useful is situations where extremely fast frequency converter response and precise speed control are required I...

Page 166: ...o react on messages during the auto tuning sequence Enabling auto tuning parameter XC 09 PID Autotuning puts the relevant PID controller into PID auto tuning mode The keypad then provides on screen instructions PID auto tuning functions by introducing step changes and then monitoring the feedback Based on the feedback response the following required values are calculated PID proportional gain Para...

Page 167: ...999999 999 par XC 04 Enter the minimum allowable feedback level in user units as defined in Parameter XC 10 Ext 1 Ref Feedback Unit for EXT CL 1 Parameter XC 30 Ext 2 Ref Feedback Unit for EXT CL 2 Parameter XC 50 Ext 3 Ref Feedback Unit for EXT CL 3 If the level drops below parameter XC 03 Minimum Feedback Level PID auto tuning is aborted and an error message appears in the keypad XC 04 Maximum F...

Page 168: ... min 145 ft 160 F 170 psi 171 lb in2 172 in WG 173 ft WG 174 in Hg 180 HP XC 11 Ext 1 Minimum Reference Range Function 0 ExtPID1Unit 999999 999 par XC 12 ExtPID1Unit Select the minimum reference for the closed loop 1 controller XC 12 Ext 1 Maximum Reference Range Function 100 ExtPID1Unit par XC 11 999999 999 ExtPID1Unit NOTICE Set the value for parameter XC 12 Ext 1 Maximum Reference before settin...

Page 169: ...ce is used in extended 1 closed loop Ext 1 setpoint is added to the value from the Ext 1 Reference source selected in parameter XC 13 Ext 1 Reference Source XC 17 Ext 1 Reference Unit Range Function 0 ExtPID1Unit 999999 999 999999 999 ExtPID1Unit Readout of the reference value for the closed loop 1 controller XC 18 Ext 1 Feedback Unit Range Function 0 ExtPID1Unit 999999 999 999999 999 ExtPID1Unit ...

Page 170: ...differentiator does not react to a constant error It only provides a gain when the feedback changes The quicker the feedback changes the stronger the gain from the differentiator XC 24 Ext 1 Dif Gain Limit Range Function 5 1 50 Set a limit for the differentiator gain DG The DG increases if there are fast changes Limit the DG to obtain a pure differentiator gain when changes are slow and a constant...

Page 171: ... 2 Reference Unit Range Function 0 ExtPID2Unit 999999 999 999999 999 ExtPID2Unit See parameter XC 17 Ext 1 Reference Unit Ext 1 Reference Unit for details XC 38 Ext 2 Feedback Unit Range Function 0 ExtPID2Unit 999999 999 999999 999 ExtPID2Unit See parameter XC 18 Ext 1 Feedback Unit for details XC 39 Ext 2 Output Range Function 0 0 100 See parameter XC 19 Ext 1 Output for details 3 23 5 XC 4 Ext C...

Page 172: ...ls 0 No function 1 Analog Input 53 2 Analog Input 54 7 Pulse input 29 8 Pulse input 33 20 Digital Potentiometer 21 Analog input X30 11 22 Analog input X30 12 23 Analog Input X42 1 24 Analog Input X42 3 25 Analog Input X42 5 30 Ext Closed Loop 1 31 Ext Closed Loop 2 32 Ext Closed Loop 3 XC 54 Ext 3 Feedback Source Option Function See parameter XC 14 Ext 1 Feedback Source for details 0 No function 1...

Page 173: ...ontrol for details 0 Normal 1 Inverse XC 61 Ext 3 Proportional Gain Range Function 0 01 0 10 See parameter XC 21 Ext 1 Proportional Gain for details XC 62 Ext 3 Integral Time Range Function 10000 s 0 01 10000 s See parameter XC 22 Ext 1 Integral Time for details XC 63 Ext 3 Differentation Time Range Function 0 s 0 10 s See parameter XC 23 Ext 1 Differentation Time for details XC 64 Ext 3 Dif Gain ...

Page 174: ...meters in parameter group PC 2 Bandwidth Settings and PC 4 Staging Settings often depend on the dynamic of the system and final adjustment to be done at the commissioning of the plant NOTICE The Pump Controller is supposed to operate in closed loop controlled by the built in PI controller 3 closed loop selected in parameter H 40 Configuration Mode If 0 open loop is selected in parameter H 40 Confi...

Page 175: ...d Pump Option Function Fixed lead pump is a configuration when the variable speed pump is connected directly to the frequency converter and if a contactor is applied between frequency converter and pump this contactor is not controlled by the frequency converter If operating with parameter PC 50 Lead Pump Alternation set to other than 0 Off set this parameter to 0 No 0 No The lead pump function ca...

Page 176: ...meter F 52 Minimum Reference and parameter F 53 Maximum Reference PC 21 Override Bandwidth Range Function Illustration 3 63 Setting the OBW too close to the SBW could defeat the purpose with frequent staging at momentary pressure changes Setting the OBW too high might lead to unacceptably high or low pressure in the system while the SBW timers are running The value can be optimised with increased ...

Page 177: ...ight exceed the override bandwidth OBW It is not recommended to destage a pump in response to a staging pressure peak The OBW time can be PC 25 OBW Time Range Function programmed to prevent staging until the system pressure has stabilised and normal control established Set the timer to a value that allows the system to stabilise after staging The 10 s factory setting is appropriate in most applica...

Page 178: ...r Speed Low Limit Hz with 1 or more fixed speed pumps in operation and system requirements satisfied In this situation the adjustable speed pump contributes a little to the system When the programmed value of the timer expires a stage is removed avoiding dead head water circulation in the adjustable speed pump Illustration 3 67 Destage Function Time 3 24 4 PC 4 Staging Settings Parameters determin...

Page 179: ...and nHIGH is Motor Speed High Limit Illustration 3 70 Staging Threshold NOTICE If the setpoint is reached after staging before the variable speed pump reaches its minimum speed the system enters the state closed loop as soon as the feedback pressure is crossing the set point PC 43 Destaging Threshold Range Function 50 0 100 When removing a fixed speed pump to prevent an undershoot of pressure the ...

Page 180: ...ing speed the fixed speed pump is destaged Destaging speed is calculated based on parameter PC 43 Destaging Threshold and parameter F 17 Motor Speed High Limit RPM Destaging speed is calculated with the following formula DESTAGE HIGH DESTAGE 100 where nHIGH is motor speed high limit and nDESTAGE100 is the value of destaging threshold PC 47 Destaging Speed Hz Range Function 0 Hz 0 0 Hz Readout of t...

Page 181: ...nt the alternation of the variable speed pump takes place every time the alternation time interval expires can be checked in parameter PC 53 Alternation Timer Value PC 53 Alternation Timer Value Range Function 0 0 7 Read out parameter for the alternation time interval value set in parameter PC 52 Alternation Time Interval PC 54 Alternation Predefined Time Range Function 0 0 0 If selecting 3 Predef...

Page 182: ...s different from 0 Off This parameter sets the time between stopping the old variable speed pump and starting this pump as a new fixed speed PC 59 Run on Line Delay Range Function pump Refer to Illustration 3 73 for description of staging and alternation 3 24 6 PC 8 Status Readout parameters informing about the operating status of the Pump Controller and the pumps controlled PC 80 Pump Status Rang...

Page 183: ... 1 Do reset 3 24 7 PC 9 Service Parameters used in case of service on 1 or more of the pumps controlled PC 90 Pump Interlock Array 10 Option Function In this parameter it is possible to disable 1 or more of the fixed lead pumps For example the pump is not selected for staging on even if it is the next pump in the operation sequence It is not possible to disable the lead pump with the pump interloc...

Page 184: ...Controller Mode The LC stops when the stop event parameter LC 02 Stop Event is TRUE Parameter LC 03 Reset Logic Controller resets all LC parameters and starts programming from scratch 3 25 2 LC 0 LC Settings Use the LC settings to activate deactivate and reset the Logic Controller LC 00 Logic Controller Mode Option Function 0 Off Disables the logic controller 1 On Enables the logic controller LC 0...

Page 185: ...rter is tripped but not trip locked and Reset is pressed 42 Auto Reset Trip This event is TRUE if the frequency converter is tripped but not trip locked and an automatic reset is issued 43 OK Key This event is TRUE if OK is pressed LC 01 Start Event Option Function 44 Reset Key This event is TRUE if Reset is pressed 45 Left Key This event is TRUE if is pressed 46 Right Key This event is TRUE if is...

Page 186: ...r Time out 1 Use the result of timer 1 in the logic rule 32 Logic Controller Time out 2 Use the result of timer 2 in the logic rule 33 Digital input DI18 Use the value of DI 18 in the logic rule High TRUE 34 Digital input DI19 Use the value of DI 19 in the logic rule High TRUE 35 Digital input DI27 Use the value of DI 27 in the logic rule High TRUE 36 Digital input DI29 Use the value of DI 29 in t...

Page 187: ...bles that is output frequency output current analog input and so on to fixed preset values Illustration 3 75 Comparators There are digital values that are compared to fixed time values See explanation in parameter LC 10 Comparator Operand Comparators are evaluated once in each scan interval Use the result true or false directly All parameters in this parameter group are array parameters with index...

Page 188: ...put DI29 134 Digital input DI32 135 Digital input DI33 150 Logic Controller digital output A 151 Logic Controller digital output B 152 Logic Controller digital output C 153 Logic Controller digital output D 154 Logic Controller digital output E 155 Logic Controller digital output F 160 Relay 1 161 Relay 2 180 Local referecnce active 181 Remote reference active 182 Start command 183 Drive stopped 1...

Page 189: ... Rule Boolean 2 and parameter LC 44 Logic Rule Boolean 3 Define the operators used to logically combine the selected inputs in parameter LC 41 Logic Rule Operator 1 and parameter LC 43 Logic Rule Operator 2 Illustration 3 76 Logic Rules Priority of calculation The results of parameter LC 40 Logic Rule Boolean 1 parameter LC 41 Logic Rule Operator 1 and parameter LC 42 Logic Rule Boolean 2 are calc...

Page 190: ... input fieldbus or other 40 Drive stopped This logic rule is TRUE if the frequency converter is stopped or coasted either via digital input fieldbus or other LC 40 Logic Rule Boolean 1 Array 6 Option Function 41 Reset Trip This logic rule is TRUE if the frequency converter is tripped but not trip locked and Reset is pressed 42 Auto Reset Trip This logic rule is TRUE if the frequency converter is t...

Page 191: ...s the expression NOT LC 40 OR NOT LC 42 LC 42 Logic Rule Boolean 2 Array 6 Option Function Select the second boolean TRUE or FALSE input for the selected logic rule See parameter LC 40 Logic Rule Boolean 1 for further descriptions of choices and their functions LC 43 Logic Rule Operator 2 Array 6 Option Function Select the 2nd logical operator to be used on the boolean input calculated in Paramete...

Page 192: ...y 20 Option Function 42 Auto Reset Trip 43 OK Key 44 Reset Key 45 Left Key 46 Right Key 47 Up Key 48 Down Key 50 Comparator 4 51 Comparator 5 60 Logic rule 4 61 Logic rule 5 70 Logic Controller Time out 3 71 Logic Controller Time out 4 72 Logic Controller Time out 5 73 Logic Controller Time out 6 74 Logic Controller Time out 7 76 Digital Input x30 2 77 Digital Input x30 3 78 Digital Input x30 4 80...

Page 193: ...tion Function 31 Start timer 2 Starts timer 2 see parameter LC 20 Logic Controller Timer for further description 32 Set digital out A low Any output with digital output 1 selected is low off 33 Set digital out B low Any output with digital output 2 selected is low off 34 Set digital out C low Any output with digital output 3 selected is low off 35 Set digital out D low Any output with digital outp...

Page 194: ...ut 7 90 ECB Drive Mode 91 ECB Bypass Mode LC 91 Alert Action Array 10 Select the action that the frequency converter performs when the event defined in parameter LC 90 Alert Trigger occurs Option Function 0 Info 1 Warning 2 Freeze output 3 Freeze output warn 4 Stop 5 Stop warning 6 Jogging 7 Jogging warning 8 Max speed 9 Max speed warn 10 Stop and trip 11 Stop and trip w manual reset 12 Trip 13 Tr...

Page 195: ...the time period set in parameter B 02 DC Braking Time B 02 DC Braking Time Range Function 10 s 0 60 s Set the duration of the DC brake current set in parameter B 01 DC Brake Current once activated B 03 DC Brake Cut In Speed RPM Range Function 0 RPM 0 0 RPM Set the DC brake cut in speed for activation of the DC braking current set in parameter B 01 DC Brake Current upon a stop command When paramete...

Page 196: ...e resistance of the brake resistor tbr is the active breaking time within the 120 s period Tbr B 12 Brake Power Limit kW Range Function Ubr is the DC voltage where the brake resistor is active This depends on the unit as follows 200 240 V 390 V 380 500 V 810 V 525 600 V 943 V 525 690 V 1099 V NOTICE If Rbr is not known or if Tbr is different from 120 s the practical approach is to run the brake ap...

Page 197: ... appears 1 Warning Monitors brake resistor and brake IGBT for a short circuit and runs a test for brake resistor disconnection during power up 2 Trip Monitors for a short circuit or disconnection of the brake resistor or a short circuit of the brake IGBT If a fault occurs the frequency converter cuts out while showing an alarm trip lock 3 Stop and trip Monitors for a short circuit or disconnection...

Page 198: ...arms that are trip locked offer additional protection means that the mains supply must be switched off before the alarm can be reset After being switched back on the frequency converter is no longer blocked and may be reset as described above once the cause has been rectified Alarms that are not trip locked can also be reset using the automatic reset function in parameter H 04 Auto Reset Times War...

Page 199: ... Parameter H 78 Missin g Motor Phase Function 32 Motor phase W missing X X X Parameter H 78 Missin g Motor Phase Function 33 Inrush fault X X 34 Network communication fault X X 35 Option fault X 36 Mains failure X X parameter SP 10 Line failure 38 Internal fault X X 40 Overload T27 X 41 Overload T29 X 42 Overload X30 6 7 X 45 Earth fault 2 X X 47 24 V supply low X X X 48 1 8 V supply low X X 49 Sp...

Page 200: ...en Belt X X Par AP 6 96 Start Delayed X Par AP 7 97 Stop Delayed X Par AP 7 98 Clock Fault X K 7 200 Fire Mode X FB 0 201 Fire Mode was Active X K 7 202 Fire Mode Limits Exceeded X K 7 250 New spare part X X 251 New model number X X Table 4 1 Alarm Warning code list X Dependent on parameter LED indication Warning yellow Alarm flashing red Trip locked yellow and red Table 4 2 Troubleshooting AF 600...

Page 201: ...e Fault 01000000 02000000 VDD supply low 04000000 Not used 08000000 Not used 10000000 Earth fault DESAT 20000000 Drive restored 80000000 Table 4 3 Parameter DR 90 Alarm Word Bit hex Alarm word 2 parameter DR 91 Alarm Word 2 00000001 00000002 Reserved 00000004 Service Trip Typecode Sparepart 00000008 Reserved 00000010 Reserved 00000020 00000040 00000080 00000100 Broken Belt 00000200 Not used 000004...

Page 202: ...000 10000000 20000000 80000000 Not used Table 4 5 parameter DR 92 Warning Word Bit Hex Warning Word 2 parameter DR 93 Warning Word 2 00000001 00000002 00000004 Clock Failure 00000008 Reserved 00000010 Reserved 00000020 00000040 00000080 End of Curve 00000100 Broken Belt 00000200 Not used 00000400 Reserved 00000800 Reserved 00001000 Reserved 00002000 Reserved 00004000 Reserved 00008000 Reserved 000...

Page 203: ...eserved 10000000 Reserved 20000000 Reserved 40000000 Reserved 80000000 Reserved Table 4 7 Parameter DR 94 Ext Status Word Bit hex Extended status word 2 parameter DR 95 Ext Status Word 2 00000001 Off 00000002 Hand Auto 00000004 Not used 00000008 Not used 00000010 Not used 00000020 Relay 123 active 00000040 Start Prevented 00000080 Control ready 00000100 Drive ready 00000200 Quick Stop 00000400 DC ...

Page 204: ...he frequency converter trips after a certain time Troubleshooting Extend the ramp time Change the ramp type Activate the functions in parameter B 10 Brake Function Increase parameter SP 26 Trip Delay at Drive Fault If the alarm warning occurs during a power sag use kinetic back up parameter SP 10 Line failure WARNING ALARM 8 DC under voltage If the DC link voltage drops below the undervoltage limi...

Page 205: ...uency converter trips and issues an alarm Shock loading or quick acceleration with high inertia loads can cause this fault If the acceleration during ramp up is quick the fault can also appear after kinetic back up If extended mechanical brake control is selected a trip can be reset externally Troubleshooting Remove the power and check if the motor shaft can be turned Check that the motor size mat...

Page 206: ...ly at start up Check the sensors on the control card WARNING 24 External fan fault The fan warning function is a protective function that checks if the fan is running mounted The fan warning can be disabled in parameter SP 53 Fan Monitor 0 Disabled For frequency converters with DC fans there is a feedback sensor mounted in the fan If the fan is commanded to run and there is no feedback from the se...

Page 207: ...service department Note the code number for further trouble shooting directions Number Text 0 Serial port cannot be restore Contact your GE supplier or GE service department 256 258 Power EEPROM data is defective or too old Replace power card 512 519 Internal fault Contact your GE supplier or GE service department 783 Parameter value outside of min max limits 1024 1284 Internal fault Contact your ...

Page 208: ...opping the frequency converter trips ALARM 50 Auto tune calibration failed Contact the GE supplier or GE service department ALARM 51 Auto tune check Unom and Inom The settings for motor voltage motor current and motor power are wrong Troubleshooting Check the settings in parameters P 02 P 03 P 06 P 07 F 04 and F 05 ALARM 52 Auto tune low Inom The motor current is too low Troubleshooting Check the ...

Page 209: ...t the system and reset the frequency converter after clearing the fault ALARM 93 Dry pump A no flow condition in the system with the frequency converter operating at high speed may indicate a dry pump Parameter AP 26 Dry Pump Function is set for alarm Troubleshooting Troubleshoot the system and reset the frequency converter after clearing the fault ALARM 94 End of curve The feedback is lower than ...

Page 210: ...he correct type code in parameter SP 23 Typecode Setting according to the label on the frequency converter Remember to select Save to EEPROM at the end WARNING 251 New typecode The power card or other components are replaced and the type code has changed Troubleshooting AF 600 FP Programming Guide DET 620D 03 2016 All rights reserved 209 4 4 ...

Page 211: ...s may be found in chapter 5 1 Parameter Options K Keypad Set up F Fundamental Parameters E Digital In Outs C Frequency Control Functions P Motor Data H High Perf Parameters AN Analog In Out SP Special Functions O Options Comms AO Analog I O Options PB PROFIdrive EN Ethernet LN LonWorks BN BACnet DN DeviceNet ID Drive Information DR Data Readouts LG Logs I O Opt Status AP HVAC Appl Param FB Fire By...

Page 212: ...dout 1 All set ups TRUE Uint8 K 31 Min Value of Custom Readout ExpressionLimit All set ups TRUE 2 Int32 K 32 Max Value of Custom Readout 100 CustomReadoutUnit All set ups TRUE 2 Int32 K 37 Display Text 1 0 N A 1 set up TRUE 0 VisStr 25 K 38 Display Text 2 0 N A 1 set up TRUE 0 VisStr 25 K 39 Display Text 3 0 N A 1 set up TRUE 0 VisStr 25 K 4 K 40 Hand Button on Keypad 1 Enabled All set ups TRUE Ui...

Page 213: ...1 F 10 Electronic Overload ExpressionLimit All set ups TRUE Uint8 F 11 Motor External Fan 0 No All set ups TRUE Uint8 F 12 Motor Thermistor Input 0 None All set ups TRUE Uint8 F 15 Motor Speed High Limit Hz ExpressionLimit All set ups TRUE 1 Uint16 F 16 Motor Speed Low Limit Hz ExpressionLimit All set ups TRUE 1 Uint16 F 17 Motor Speed High Limit RPM ExpressionLimit All set ups TRUE 67 Uint16 F 18...

Page 214: ...l set ups TRUE Uint8 E 24 Function Relay ExpressionLimit All set ups TRUE Uint8 E 26 On Delay Relay 0 01 s All set ups TRUE 2 Uint16 E 27 Off Delay Relay 0 01 s All set ups TRUE 2 Uint16 E 5 E 51 Terminal 27 Mode 0 Input All set ups TRUE Uint8 E 52 Terminal 29 Mode 0 Input All set ups TRUE Uint8 E 53 Terminal X30 2 Digital Input ExpressionLimit All set ups TRUE Uint8 E 54 Terminal X30 3 Digital In...

Page 215: ...7 Uint16 C 03 Jump Speed To RPM ExpressionLimit All set ups TRUE 67 Uint16 C 04 Jump Frequency To Hz ExpressionLimit All set ups TRUE 1 Uint16 C 05 Multi step Frequency 1 8 0 All set ups TRUE 2 Int16 C 2 C 20 Jog Speed Hz ExpressionLimit All set ups TRUE 1 Uint16 C 21 Jog Speed RPM ExpressionLimit All set ups TRUE 67 Uint16 C 22 Jog Accel Decel Time ExpressionLimit All set ups TRUE 2 Uint32 C 23 Q...

Page 216: ...pressionLimit All set ups TRUE Uint8 P 63 Locked Rotor Detection Time s ExpressionLimit All set ups TRUE 2 Uint8 5 1 7 H High Perf Parameters Par No Parameter description Default value 4 set up Change during operation Conver sion index Type H 0 H 01 Option Detection 0 Protect Option Config 1 set up TRUE Uint8 H 03 Restore Factory Settings 0 Normal operation All set ups TRUE Uint8 H 04 Auto Reset T...

Page 217: ...s TRUE 0 Uint16 5 1 8 AN Analog In Out Par No Parameter description Default value 4 set up Change during operation Conver sion index Type AN 0 AN 00 Live Zero Timeout Time 10 s All set ups TRUE 0 Uint8 AN 01 Live Zero Timeout Function 0 Off All set ups TRUE Uint8 AN 02 Fire Mode Live Zero Timeout Function 0 Off All set ups TRUE Uint8 AN 1 AN 10 Terminal 53 Low Voltage 0 07 V All set ups TRUE 2 Int...

Page 218: ...All set ups TRUE Uint8 AN 61 Terminal X30 8 Min Scale 0 All set ups TRUE 2 Int16 AN 62 Terminal X30 8 Max Scale 100 All set ups TRUE 2 Int16 AN 63 Terminal X30 8 Output Bus Control 0 All set ups TRUE 2 N2 AN 64 Terminal X30 8 Output Timeout Preset 0 1 set up TRUE 2 Uint16 5 1 9 SP Special Functions Par No Parameter description Default value 4 set up Change during operation Conver sion index Type S...

Page 219: ... Uint8 O 06 Reset Control Word Timeout 0 Do not reset All set ups TRUE Uint8 O 07 Diagnosis Trigger 0 Disable 2 set ups TRUE Uint8 O 08 Readout Filtering ExpressionLimit All set ups TRUE Uint8 O 09 Communication Charset 1 ANSI X3 4 2 set ups TRUE Uint8 O 1 O 10 Control Word Profile 0 Drive Profile All set ups TRUE Uint8 O 13 Configurable Status Word STW 1 Profile Default All set ups TRUE Uint8 O 1...

Page 220: ...ps TRUE 2 Int16 AO 14 Term X42 1 Low Ref Feedb Value 0 N A All set ups TRUE 3 Int32 AO 15 Term X42 1 High Ref Feedb Value 100 N A All set ups TRUE 3 Int32 AO 16 Term X42 1 Filter Time Constant 0 001 s All set ups TRUE 3 Uint16 AO 17 Term X42 1 Live Zero 1 Enabled All set ups TRUE Uint8 AO 2 AO 20 Terminal X42 3 Low Voltage 0 07 V All set ups TRUE 2 Int16 AO 21 Terminal X42 3 High Voltage 10 V All ...

Page 221: ...or Counter 0 N A All set ups TRUE 0 Uint8 DN 06 Readout Receive Error Counter 0 N A All set ups TRUE 0 Uint8 DN 07 Readout Bus Off Counter 0 N A All set ups TRUE 0 Uint8 DN 1 DN 10 Process Data Type Selection ExpressionLimit All set ups TRUE Uint8 DN 11 Process Data Config Write ExpressionLimit 2 set ups TRUE Uint16 DN 12 Process Data Config Read ExpressionLimit 2 set ups TRUE Uint16 DN 13 Warning...

Page 222: ... A All set ups TRUE 0 Uint16 PB 65 Profile Number 0 N A All set ups TRUE 0 OctStr 2 PB 67 Control Word 1 0 N A All set ups TRUE 0 V2 PB 68 Status Word 1 0 N A All set ups TRUE 0 V2 PB 7 PB 70 Edit Set up 9 Active Set up All set ups TRUE Uint8 PB 71 Profibus Save Data Values 0 Off All set ups TRUE Uint8 PB 72 ProfibusDriveReset 0 No action 1 set up FALSE Uint8 PB 75 DO Identification 0 N A All set ...

Page 223: ... TRUE 0 OctStr 4 EN 28 Store Data Values 0 Off All set ups TRUE Uint8 EN 29 Store Always 0 Off 1 set up TRUE Uint8 EN 3 EN 30 Warning Parameter 0 N A All set ups TRUE 0 Uint16 EN 31 Net Reference 0 Off 2 set ups TRUE Uint8 EN 32 Net Control 0 Off 2 set ups TRUE Uint8 EN 33 CIP Revision ExpressionLimit All set ups TRUE 0 Uint16 EN 34 CIP Product Code ExpressionLimit 1 set up TRUE 0 Uint16 EN 35 EDS...

Page 224: ... Word 0 N A All set ups TRUE 0 Uint16 LN 17 XIF Revision 0 N A All set ups TRUE 0 VisStr 5 LN 18 LonWorks Revision 0 N A All set ups TRUE 0 VisStr 5 LN 2 LN 21 Store Data Values 0 Off All set ups TRUE Uint8 5 1 17 ID Drive Information Par No Parameter description Default value 4 set up Change during operation Conver sion index Type ID 0 ID 00 Operating hours 0 h All set ups FALSE 74 Uint32 ID 01 R...

Page 225: ...sStr 20 ID 5 ID 50 SW ID Power Card 0 N A All set ups FALSE 0 VisStr 20 ID 51 Drive Serial Number 0 N A All set ups FALSE 0 VisStr 10 ID 53 Power Card Serial Number 0 N A All set ups FALSE 0 VisStr 19 ID 59 Filename ExpressionLimit 1 set up FALSE 0 VisStr 16 ID 6 ID 60 Option Mounted 0 N A All set ups FALSE 0 VisStr 30 ID 61 Option SW Version 0 N A All set ups FALSE 0 VisStr 20 ID 62 Option Orderi...

Page 226: ...t8 DR 32 Brake Energy s 0 kW All set ups FALSE 0 Uint32 DR 33 Brake Energy Average 0 kW All set ups FALSE 0 Uint32 DR 34 Heatsink Temp 0 C All set ups FALSE 100 Uint8 DR 35 Drive Thermal 0 All set ups FALSE 0 Uint8 DR 36 Drive Nominal Current ExpressionLimit All set ups FALSE 2 Uint32 DR 37 Drive Max Current ExpressionLimit All set ups FALSE 2 Uint32 DR 38 Logic Controller State 0 N A All set ups ...

Page 227: ...DR 84 Comm Option STW 0 N A All set ups FALSE 0 V2 DR 85 Drive Port CTW 1 0 N A All set ups FALSE 0 V2 DR 86 Drive Port REF 1 0 N A All set ups FALSE 0 N2 DR 9 DR 90 Alarm Word 0 N A All set ups FALSE 0 Uint32 DR 91 Alarm Word 2 0 N A All set ups FALSE 0 Uint32 DR 92 Warning Word 0 N A All set ups FALSE 0 Uint32 DR 93 Warning Word 2 0 N A All set ups FALSE 0 Uint32 DR 94 Ext Status Word 0 N A All ...

Page 228: ... Uint32 AP 35 Low Speed Power HP ExpressionLimit All set ups TRUE 2 Uint32 AP 36 High Speed RPM ExpressionLimit All set ups TRUE 67 Uint16 AP 37 High Speed Hz ExpressionLimit All set ups TRUE 1 Uint16 AP 38 High Speed Power kW ExpressionLimit All set ups TRUE 1 Uint32 AP 39 High Speed Power HP ExpressionLimit All set ups TRUE 2 Uint32 AP 4 AP 40 Minimum Run Time 10 s All set ups TRUE 0 Uint16 AP 4...

Page 229: ...set ups TRUE 3 Int32 5 1 21 FB Fire Bypass Operation Par No Parameter description Default value 4 set up Change during operation Conver sion index Type FB 0 FB 00 Fire Mode Function 0 Disabled 2 set ups TRUE Uint8 FB 01 Fire Mode Configuration 0 Open Loop All set ups TRUE Uint8 FB 02 Fire Mode Unit ExpressionLimit All set ups TRUE Uint8 FB 03 Fire Mode Min Reference ExpressionLimit All set ups TRU...

Page 230: ...m Bin Value ExpressionLimit 2 set ups TRUE 0 Uint8 T 66 Reset Continuous Bin Data 0 Do not reset All set ups TRUE Uint8 T 67 Reset Timed Bin Data 0 Do not reset All set ups TRUE Uint8 T 8 T 80 Power Reference Factor 100 2 set ups TRUE 0 Uint8 T 81 Energy Cost 1 N A 2 set ups TRUE 2 Uint32 T 82 Investment 0 N A 2 set ups TRUE 0 Uint32 T 83 Energy Savings 0 kWh All set ups TRUE 75 Int32 T 84 Cost Sa...

Page 231: ...TRUE Uint8 CL 8 CL 81 PID Normal Inverse Control 0 Normal All set ups TRUE Uint8 CL 82 PID Start Speed RPM ExpressionLimit All set ups TRUE 67 Uint16 CL 83 PID Start Speed Hz ExpressionLimit All set ups TRUE 1 Uint16 CL 84 On Reference Bandwidth 5 All set ups TRUE 0 Uint8 CL 9 CL 91 PID Anti Windup 1 On All set ups TRUE Uint8 CL 93 PID Proportional Gain 0 50 N A All set ups TRUE 2 Uint16 CL 94 PID...

Page 232: ...et ups TRUE 3 Int32 XC 39 Ext 2 Output 0 All set ups TRUE 0 Int32 XC 4 XC 40 Ext 2 Normal Inverse Control 0 Normal All set ups TRUE Uint8 XC 41 Ext 2 Proportional Gain 0 01 N A All set ups TRUE 2 Uint16 XC 42 Ext 2 Integral Time 10000 s All set ups TRUE 2 Uint32 XC 43 Ext 2 Differentation Time 0 s All set ups TRUE 2 Uint16 XC 44 Ext 2 Dif Gain Limit 5 N A All set ups TRUE 1 Uint16 XC 5 XC 50 Ext 3...

Page 233: ...8 PC 3 PC 30 Destage Function Time 15 s All set ups TRUE 0 Uint16 PC 4 PC 40 Decel Ramp Delay 10 s All set ups TRUE 1 Uint16 PC 41 Accel Ramp Delay 2 s All set ups TRUE 1 Uint16 PC 42 Staging Threshold ExpressionLimit All set ups TRUE 0 Uint8 PC 43 Destaging Threshold ExpressionLimit All set ups TRUE 0 Uint8 PC 44 Staging Speed RPM 0 RPM All set ups TRUE 67 Uint16 PC 45 Staging Speed Hz 0 Hz All s...

Page 234: ...t8 LC 11 Comparator Operator ExpressionLimit 2 set ups TRUE Uint8 LC 12 Comparator Value ExpressionLimit 2 set ups TRUE 3 Int32 LC 2 LC 20 Logic Controller Timer ExpressionLimit 1 set up TRUE 3 TimD LC 4 LC 40 Logic Rule Boolean 1 ExpressionLimit 2 set ups TRUE Uint8 LC 41 Logic Rule Operator 1 ExpressionLimit 2 set ups TRUE Uint8 LC 42 Logic Rule Boolean 2 ExpressionLimit 2 set ups TRUE Uint8 LC ...

Page 235: ...et ups TRUE 1 Uint16 B 06 Parking Current 50 All set ups TRUE 0 Uint16 B 07 Parking Time 3 s All set ups TRUE 1 Uint16 B 1 B 10 Brake Function ExpressionLimit All set ups TRUE Uint8 B 11 Brake Resistor ohm ExpressionLimit All set ups TRUE 2 Uint32 B 12 Brake Power Limit kW ExpressionLimit All set ups TRUE 0 Uint32 B 13 Braking Thermal Overload 0 Off All set ups TRUE Uint8 B 15 Brake Check 0 Off Al...

Page 236: ... Default settings 23 DeviceNet 94 Display Line 1 2 Small 0 21 29 Display Line 1 3 Small 0 22 29 Display Line 2 Large 0 23 29 Drive bypass 141 Drive closed loop 154 Dry pump function 127 E Electrical terminals 9 End of curve 132 Energy saving VT 65 Energy savings 78 Ethernet 103 105 Ethernet IP 104 ETR 116 Extended CL autotuning 165 F Feedback 154 157 206 208 Fieldbus 51 Fire mode 138 208 Forward O...

Page 237: ... 113 Parameter selection 21 Parameter set up 16 Phase loss 203 PID autotuning 161 PID basic settings 162 PID closed loop 154 PID controller 163 Protection mode 8 Pump controller 173 Q Quick menu mode 13 16 R Rated motor speed 5 RCD 6 Reference 104 Relay outputs 45 Reset 203 204 208 Restore 23 S Safety precautions 7 Screened armoured 10 Serial communication 5 Short circuit Short circuit 204 Short c...

Page 238: ...Index AF 600 FP Programming Guide DET 620D 03 2016 All rights reserved 237 ...

Page 239: ...d or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE company AF 600 FP are trademarks of the General Electric Company GE 41 Woodford Avenue Plainville CT 06062 www geindustrial com drives 130R0359 MG11S502 DET 620D GE Industrial Solutions AF 600 FPTM Fan Pump Drive Programming Guide AF 600 FP TM Fan and Pump D...

Reviews: