88 Program features
Connection of motor temperature sensor to the drive via a relay
PTC alternative A: This table shows the insulation requirement for a customer’s
external relay, and the insulation requirement for the sensor to fulfill decisive voltage
class A (double insulation) of IEC 60800-5-1.
PTC alternative B: Decisive voltage class B of IEC 60800-5-1 (basic insulation) is
provided with a 6 kV relay. Circuits connected to all motor protection relay inputs and
outputs must be protected against direct contact.
Pt100 alternative A: This table shows the insulation requirement for a customer’s
external relay, and the insulation requirement for the sensor to fulfill decisive voltage
class A (double insulation) of IEC 60800-5-1.
Pt100 alternative B: Decisive voltage class B of IEC 60800-5-1 (basic insulation) can
be achieved when there is basic insulation between the sensor and live parts of the
motor. Circuits connected to all motor protection relay inputs and outputs must be
protected against direct contact.
Settings and diagnostics
Menu
-
Primary settings
-
Motor
-
Thermal protection estimated
,
Menu
-
Primary settings
-
Motor
-
Thermal protection measured
Settings
Parameter group
(page
Motor overload protection
This section describes motor overload protection without using motor thermal
protection model, either with estimated or measured temperature. For protection with
the motor thermal protection model, see section
on page
Motor overload protection is required and specified by multiple standards including
the US National Electric Code (NEC), UL 508C and the common UL\IEC 61800-5-1
standard in conjunction with IEC 60947-4-1. The standards allow for motor overload
protection without external temperature sensors.
The protection feature allows the user to specify the class of operation in the same
manner as the overload relays are specified in standards IEC 60947-4-1 and NEMA
ICS 2.
PTC relay
Temperature sensor insulation requirement
Type
Insulation
External relay
Basic insulation 6 kV
Basic insulation
Pt100 relay
Temperature sensor insulation requirement
between sensor and live parts of motor
Type
Insulation
External relay
Basic insulation 6 kV
Basic insulation
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...