Program features 49
User Load Curve
The User Load Curve (ULC) provides a supervisory function that monitors an input
signal as a function of speed and load. The ULC consists of an overload and an
underload curve, or just one of them.
Note:
This feature is available only in vector control mode.
Some of the salient features of the ULC are:
• Formed by five points -The underload and overload curve are formed by five
points where the points represent monitored signal as a function of speed.
• Warning and/or fault for overload and underload - A warning and/or fault can be
displayed, if the monitored signal stays continuously over the overload/underload
limit for a defined time. You can define the time in parameter
and the action in parameter
/
• Sector based warning / fault - The five points makes four sectors and a warning
and/or fault can be displayed at each sector. This helps to find the speed range
that causes the fault or warning and the investigation can be performed
accordingly.
For example, overload can be used to monitor for saw blade hitting a knot or fan load
profiles becoming too high. Underload can be used to monitor for load dropping and
breaking of conveyer belts or fan belts.
The below graph shows the underload and overload points in a user load curve.
Overload area
Underload area
Allowed operating area
(N1, OL1)
,
N2, OL2
N3, OL3
,
(N4, OL4)
,
,
(N5, OL5)
overload/underload axis (current% or torque%)
Speed, N (rpm)
Sector 1
Sector 2
Sector 3
Sector 4
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...