Fault tracing 423
AFF8
Motor heating active
Pre-heating is being performed Informative warning. Motor pre-heating is
active. Current specified by parameter
is being
passed through the motor.
AFEB Run enable missing
No run enable signal is
received.
Check setting of parameter
. Switch signal on (e.g. in
the fieldbus Control Word) or check
wiring of selected source.
AFEC External power signal
missing
set to
External 24V
but no
voltage is connected to the
control unit.
Check the external 24 V DC power
supply to the control unit, or change the
setting of parameter
.
AFED Enable to rotate
Signal to rotate has not been
received within a fixed time
delay of 120 s.
Switch enable to rotate signal on (eg. in
digital inputs).
Check the setting of (and source
selected by) parameter
AFF6
Identification run
Motor ID run will occur at next
start.
Informative warning.
B5F6
Identification run
Motor ID run completed
successfully.
Informative warning.
B5A0
STO event
Programmable event:
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is lost.
Check safety circuit connections. For
more information, see chapter
The Safe
torque off function
in the
Hardware
manual
of the drive and description of
parameter
(page
).
D501
No more available
PFC motors
No more PFC motors can be
started because they can be
interlocked or in the Hand
mode.
Check that there are no interlocked PFC
motors, see parameters:
. If
all motors are in use, the PFC system is
not adequately dimensioned to handle
the demand.
D502
All motors interlocked
All the motors in the PFC
system are interlocked.
Check that there are no interlocked PFC
motors, see parameters
D503
VSD controlled PFC
motor interlocked
The motor connected to the
drive is interlocked
(unavailable).
Motor connected to the drive is
interlocked and thus cannot be started.
Remove the corresponding interlock to
start the drive controlled PFC motor. See
parameters
…
FA90
STO diagnostics
failure
The software is not working
properly.
Restart the control unit.
Code
(hex)
Warning / Aux. code
(
aux code visible only
on assistant control
panel and drive
composer
)
Cause
What to do
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...