Fault tracing 417
A6E5
AI parametrization
The current/voltage hardware
setting of an analog input does
not correspond to parameter
settings.
Check the event log for an auxiliary code.
The code identifies the analog input
whose settings are in conflict.
Adjust either the hardware setting (on the
drive control unit) or parameter
/
.
Note:
Control board reboot (either by
cycling the power or through parameter
) is required to
validate any changes in the hardware
settings.
A6E6
ULC configuration
User load curve configuration
error.
Check the auxiliary code (format XXXX
ZZZZ). “ZZZZ” indicates the problem
(see actions for each code below).
0000 Speed points inconsistent.
Check that each speed point (parameters
…
) has a higher value than
the previous point.
0002 Underload point above
overload point.
Check that each overload point
(
) has a higher value than
the corresponding underload point
(
).
0003 Overload point below
underload point.
AFFE Override active
Override active warning.
Informative warning. See parameter
A780
Motor stall
(Programmable
warning:
Motor is operating in stall
region.
Check motor load, drive ratings and fault
function parameters.
A783
Motor overload
Motor current is too high.
Check for overloaded motor
Adjust the parameters used for the motor
overload function. (
…
,
,
)
A791
Brake resistor
Brake resistor fault.
Check brake resistor.
A792
Brake resistor wiring
Brake resistor short circuit or
fault in brake chopper.
Check brake chopper and brake resistor
connections.
A793
BR excess
temperature
Brake resistor temperature has
exceeded warning limit defined
by parameter
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameter group
).
Check warning limit setting, parameter
Check that the resistor has been
dimensioned correctly.
Check that braking cycle meets allowed
limits.
A794
BR data
Brake resistor data has not
been given.
One or more of the resistor data settings
(parameters
…
) is incorrect.
The parameter is specified by the
auxiliary code.
0000 0001 Resistance value too low.
Check value of
.
Code
(hex)
Warning / Aux. code
(
aux code visible only
on assistant control
panel and drive
composer
)
Cause
What to do
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...