Parameters 263
Selects how the drive reacts to a stall condition.
A stall condition is defined as follows:
• The drive exceeds the stall current limit (
, and
• the output frequency is below the level set by parameter
or the motor speed is below the
level set by parameter
• the conditions above have been true longer than the time
set by parameter
No action
None (stall supervision disabled).
0
Warning
The drive generates an
warning: 31.24 Stall function)
warning.
1
Fault
The drive trips on fault
.
2
Stall current limit in percent of the nominal current of the
motor. See parameter
200.0%
0.0…1600.0%
Stall current limit.
-
Stall speed limit in rpm. See parameter
150.00 rpm
0.00…10000.00
rpm
Stall speed limit.
See par.
Stall frequency limit. See parameter
.
Note:
Setting the limit below 10 Hz is not recommended.
15.00 Hz
0.00…1000.00 Hz
Stall frequency limit.
See par.
20 s
0…3600 s
Stall time.
-
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...