290 Parameters
Defines the thermal time constant for use with the motor
thermal protection model, defined as the time to reach 63% of
the nominal motor temperature. See the motor
manufacturer's recommendations.
For thermal protection according to UL requirements for
NEMA class motors, use the rule of thumb: Motor thermal
time equals 35 times t6, where t6 (in seconds) is specified by
the motor manufacturer as the time that the motor can safely
operate at six time its rated current..
256 s
100…10000 s
Motor thermal time constant.
1 = 1 s
Selects how the drive reacts when the motor reaches
overload condition.
No action
None.
0
Warning only
The drive generates an
warning when
the motor is overloaded to the warning level, that is,
parameter
reaches value 88.0%.
1
Warning and fault
The drive generates an
warning when
the motor is overloaded to the warning level, that is,
parameter
reaches value 88.0%.
Drive trips on fault
when the motor is
overloaded to the fault level, that is, parameter
reaches value 100.0%.
2
Selects the motor overload class to be used. The class of
protection is specified by the user as the time for tripping at
7.2 times (IEC 60947-4-1) or 6 times (NEMA ICS) the tripping
level current.
See section
on page
.
Class 5
Class 5 relay trip class
0
Class 10
Class 10 relay trip class
1
Class 20
Class 20 relay trip class
2
No.
Name/Value
Description
Def/FbEq16
100%
63%
100%
Time
Time
Motor thermal time
Motor current
Temperature rise
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...