280 Parameters
Source selection (see
). -
Defines the time inside which the extra time is deactivated
after extra time activation signal is switched off.
Example:
set to
is set to 00 01:30,
the extra time is active for 1 hour and 30 minutes after digital
input DI is deactivated.
00 00:00
00 00:00…07 00:00 Extra time duration.
1 = 1
35
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section
(page
).
Displays the motor temperature as estimated by the internal
motor thermal protection model (see parameters
). The unit is selected by parameter
This parameter is read-only.
0
-60…1000 °C or
-76…1832 °F
Estimated motor temperature.
1 = 1°C
Displays the temperature received through the source
defined by parameter
. The unit is
.
This parameter is read-only.
0
-60…5000 °C or
-76…9032 °F,
0...5000 ohm or
[
Measured temperature 1.
Note:
With a PTC sensor, the unit is ohms. If the measured
temperature source selection (
) is PTC analog I/O or
PTC AI/DI Voltage divider tree, the motor thermal protection
function converts the analog input signal (
) to PTC
resistance value (ohms), and shows it in this parameter. This
is the case even the parameter name and unit refer to motor
temperature (°C or °F). You cannot change the unit to ohm by
the time being (
).
1 = 1 unit
Displays the temperature received through the source
defined by parameter
. The unit
This parameter is read-only.
0
-60…5000 °C or
-76…9032 °F,
0...5000 ohm or
[
Measured temperature 2.
Note:
With a PTC sensor, the unit is ohms. If the measured
temperature source selection (
) is PTC analog I/O or
PTC AI/DI Voltage divider tree, the motor thermal protection
function converts the analog input signal (
) to PTC
resistance value (ohms), and shows it in this parameter. This
is the case even the parameter name and unit refer to motor
temperature (°C or °F). You cannot change the unit to ohm by
the time being (
).
1 = 1 unit
Motor overload level as a percentage of the fault limit.
0.0
0.0...300.0 %
Motor overload level
1 = 1unit
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...