Parameters 283
PTC analog I/O
PTC sensor connected to analog input selected by parameter
and an analog output.
The required settings are the same as with selection KTY84
analog I/O.
Note: With this selection, the control program converts the
analog signal to PTC resistance value in ohms and shows it
in parameter
The parameter name and unit still refer to
temperature.
20
PTC AI/DI Voltage
Divider tree
PTC sensor connected to the analog input selected by
parameter
. A special voltage
divider connection must be in use instead of the normal PTC
connection. The voltage divider connection uses the
ter10 V, digital input and analog input. See the drive
hardware manual for the actual connection.
This selection makes it possible to connect the PTC when no
analog output is available.
The required settings are same as with selection
Notes:
• This is applicable only for frames R0...R2.
• Make sure that the digital input that you connect to this
voltage divider circuit is not used for any other purpose in
the control program.
• With this selection, the parameter
shows PTC
resistance in ohms, not motor temperature even the
parameter name and unit still refer to temperature.
23
Defines the fault limit for temperature supervision function 1.
When measured temperature 1 exceeds the limit, the drive
trips on fault
The unit is selected by parameter
.
130 °C or
266°F or
4500 ohm
-60…5000 °C or
-76…9032 °F or
0...5000 ohm
Fault limit for temperature monitoring function 1.
Note:
If the measured temperature source selection (
) is
PTC analog I/O or PTC AI/DI Voltage divider tree, the motor
thermal protection function converts the analog input signal
(
) to PTC resistance value (ohms). Also this limit is then
a resistance value even the parameter name and unit refer to
motor temperature (°C or °F). You cannot change the unit to
ohm by the time being (
).
1 = 1 unit
Defines the warning limit for temperature supervision
function 1. When measured temperature 1 exceeds the limit,
warning
is generated.
The unit is selected by parameter
.
110°C or
230°F or
4000 ohm
-60…5000 °C or
-76…9032 °F or
0...5000 ohm
Warning limit for temperature monitoring function 1.
Note:
If the measured temperature source selection (
) is
PTC analog I/O or PTC AI/DI Voltage divider tree, the motor
thermal protection function converts the analog input signal
(
) to PTC resistance value (ohms). Also this limit is then
a resistance value even the parameter name and unit refer to
motor temperature (°C or °F). You cannot change the unit to
ohm by the time being (
).
1 = 1 unit
Specifies the analog input when the setting of
requires measurement through an
analog input.
Not selected
None.
0
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...