426 Fault tracing
3381
Output phase loss
Programmable fault:
Motor circuit fault due to
missing motor connection (any
of the three phases not
connected).
In scalar control mode, the
drive detects fault only when
the output frequency is above
10% of the motor nominal
frequency.
Connect motor cable.
If the drive is in scalar mode and nominal
current of the motor is less than 1/6 of the
nominal output current of the drive, set
parameter
4110
Control board
temperature
Control board temperature is
too high.
Check proper cooling of the drive.
Check the auxiliary cooling fan.
4210
IGBT overtemperature Estimated drive IGBT
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4290
Cooling
Drive module temperature is
excessive.
Check ambient temperature. If it exceeds
40%/104 °F (frames R4
…
R8) or if it
exceeds 50% /122 °F (frames R0
…
R8),
ensure that load current does not exceed
derated load capacity of drive. See
chapter
Technical data
, section
Derating
in the
Hardware manual
of the drive.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
42F1
IGBT temperature
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4310
Excess temperature
Power unit module
temperature is excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4380
Excess temperature
difference
High temperature difference
between the IGBTs of different
phases.
Check the motor cabling.
Check cooling of drive module(s).
4981
External temperature
1
Measured temperature 1 has
exceeded fault limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
4982
External temperature
2
Measured temperature 2 has
exceeded fault limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...