236 Parameters
Defines the maximum torque reference. Allows for local
limiting of the torque reference before it is passed on to the
torque ramp controller. For absolute torque limiting, refer to
parameter
.
300.0%
0.0…1000.0%
Maximum torque reference.
See par.
Selects torque reference source 1.
Two signal sources can be defined by this parameter and
. A digital source selected by
can be used to switch between the
two sources, or a mathematical function (
) applied to the two signals to create the reference.
Zero
None.
0
AI1 scaled
).
1
AI2 scaled
).
2
Reserved
3
FB A ref1
(see page
4
FB A ref2
(see page
5
Reserved
6…7
EFB ref1
8
EFB ref2
9
Reserved
10…14
Motor
potentiometer
(output of the motor
potentiometer).
15
PID
controller).
16
Frequency input
(when DI5 is used as a frequency
input).
17
No.
Name/Value
Description
Def/FbEq16
1
0
0
AI
FB
…
…
0
AI
FB
…
…
MUL
SUB
ADD
MIN
MAX
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...