334 Parameters
Displays the status of the EFB communication.
This parameter is read-only.
Note that the name is only visible when the error is present
(bit value is 1).
-
0000h…FFFFh
EFB communication status.
1 = 1
Displays a count of valid packets addressed to the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset down
for over 3 seconds.
-
0…4294967295
Number of received packets addressed to the drive.
1 = 1
Displays a count of valid packets transmitted by the drive.
During normal operation, this number increases constantly.
Can be reset from the control panel by keeping Reset down
for over 3 seconds.
-
0…4294967295
Number of transmitted packets.
1 = 1
Displays a count of valid packets addressed to any device on
the bus. During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset down
for over 3 seconds.
-
0…4294967295
Number of all received packets.
1 = 1
Displays a count of character errors received by the drive. An
increasing count indicates a configuration problem on the
bus.
Can be reset from the control panel by keeping Reset down
for over 3 seconds.
-
0…4294967295
Number of UART errors.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Init failed
1 = EFB initialization failed
1
Addr config err
1 = Node address not allowed by protocol
2
Silent mode
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
3
Reserved
4
Wiring error
1 = Errors detected (A/B wires possibly swapped)
5
Parity error
1 = Error detected: check parameters
6
Baud rate error
1 = Error detected: check parameters
7
No bus activity
1 = 0 bytes received during last 5 seconds
8
No packets
1 = 0 packets (addressed to any device) detected during last 5
seconds
9
Noise or addressing
error
1 = Errors detected (interference, or another device with the
same address on line)
10
Comm loss
1 = 0 packets addressed to the drive received within timeout
(
11
CW/Ref loss
1 = No control word or references received within timeout (
)
12
Not active
1 = Not active. EFB is not the active channel. Only used in
redundant communication control.
13
Protocol 1
1 = Used for protocol-dependent statuses. See protocol
documentation.
14
Protocol 2
See Bit
15
Internal error
1 = internal error. Problem with the communication to the drive
software.
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...