Fieldbus control through the embedded fieldbus interface (EFB) 451
Status Word
Status Word for the ABB Drives profile
The table below shows the fieldbus Status Word for the ABB Drives control profile.
The embedded fieldbus interface converts the drive Status Word into this form for the
fieldbus. The upper case boldface text refers to the states shown in
diagram for the ABB Drives profile
on page
.
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON
.
0
NOT READY TO SWITCH ON
.
1
RDY_RUN
1
READY TO OPERATE
.
0
OFF1 ACTIVE
.
2
RDY_REF
1
OPERATION D
.
0
OPERATION INHIBITED
.
3
TRIPPED
1
FAULT
.
0
No fault.
4
OFF_2_STATUS
1
OFF2 inactive.
0
OFF2 ACTIVE
.
5
OFF_3_STATUS
1
OFF3 inactive.
0
OFF3 ACTIVE
.
6
SWC_ON_
INHIB
1
SWITCH-ON INHIBITED
.
0
–
7
ALARM
1
Warning/Alarm.
0
No warning/alarm.
8
AT_
SETPOINT
1
OPERATING
. Actual value equals Reference (is within
tolerance limits, e.g. in speed control, speed error is
10% max. of nominal motor speed).
0
Actual value differs from Reference (is outside
tolerance limits).
9
REMOTE
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
10
ABOVE_
LIMIT
1
Actual frequency or speed equals or exceeds
supervision limit (set by drive parameter). Valid in both
directions of rotation.
0
Actual frequency or speed within supervision limit.
11
USER_0
Status bits that can be combined with drive logic for
application-specific functionality.
12
USER_1
13
USER_2
14
USER_3
15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...