Program features 45
The function is also available for scalar motor control with a frequency reference. The
input of the function is shown by
Example
A fan has vibrations in the range of 540…690 rpm and 1380…1560 rpm. To make the
drive avoid these speed ranges,
• set the critical speeds function by turning on bit 0 of parameter
, and
• set the critical speed ranges as in the figure below.
Settings
(page
• Critical frequencies: parameters
…
).
Speed controller autotune
The speed controller of the drive can be automatically adjusted using the autotune
function. Autotuning is based on an estimation of the mechanical time constant
(inertia) of the motor and machine.
The autotune routine will run the motor through a series of acceleration/deceleration
cycles, the number of which can be adjusted by parameter
. Higher values will
produce more accurate results, especially if the difference between initial and
maximum speeds is small.
The maximum torque reference used during autotuning will be the initial torque (ie.
torque when the routine is activated) plus
, unless limited by the maximum
torque limit (parameter group
) or the nominal motor torque (
).
The calculated maximum speed during the routine is the initial speed (ie. speed when
the routine is activated) +
, unless limited by parameter
540
690
1380
1560
1
Par.
= 540 rpm
2
Par.
= 690 rpm
3
Par.
= 1380 rpm
4
Par.
= 1560 rpm
1
2
3
4
(rpm)
(output of function)
(rpm)
(input of function)
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...