Program features 87
The figure and table on page 146 show typical KTY84 sensor resistance values as a
function of the motor operating temperature.
See section
Implementing a motor temperature sensor connection
on page
For the wiring of the sensor, see chapter
Electrical installation, AI1 and AI2 as Pt100,
Pt1000, Ni1000, KTY83 and KTY84 sensor inputs (X1)
in the
Hardware manual
of the
drive.
Temperature monitoring using KTY83 sensors
One KTY83 sensor can be connected to an analog input and an analog output on the
control unit.
The analog output feeds a constant excitation current of 1.0 mA through the sensor.
The sensor resistance increases as the motor temperature rises, as does the voltage
over the sensor. The temperature measurement function reads the voltage through
the analog input and converts it into degrees Celsius.
The figure and table below show typical KTY83 sensor resistance values as a
function of the motor operating temperature.
It is possible to adjust the motor temperature supervision limits and select how the
drive reacts when overtemperature is detected.
See section
Implementing a motor temperature sensor connection
on page
For the wiring of the sensor, see chapter
Electrical installation, AI1 and AI2 as Pt100,
Pt1000, Ni1000, KTY83 and KTY84 sensor inputs (X1)
in the
Hardware manual
of the
drive.
1000
2000
3000
Ohm
T
(
o
C)
-100
0
0
100
200
300
Scaling
KTY84
KTY83
°C
ohm
ohm
90
936
1569
110
1063
1774
130
1197 1993
150
1340
2225
KTY83
KTY84
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...