110 Control macros
Terminal sizes:
• (frames R0…R8: 0.14…1.5 mm
2
(all terminals)
• Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes:
1)
AI1 is used as a speed reference if vector control is selected.
2)
In scalar control (default): See
Menu - Primary settings - Start, stop, reference - Constant
frequencies
or parameter group
.
In vector control: See
Menu - Primary settings - Start, stop, reference - Constant speeds
or parameter group
.
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Only frames R6…R11 have terminals 40 and 41 for external 24 V AC/DC input.
6)
Select voltage or current for inputs AI1 and AI2 and output AO1 with parameters
and
, respectively.
7)
Total load capacity of the auxiliary voltage 24V (X2:10) = 6.0 W (250 mA /24 V). User
can use this source for either of the I/O connections (DI1... DI2- RO1 or DI3...DI6 - RO2~RO3).
8)
Input signal
9)
Output signal
Input signals
•
Analog speed/frequency reference (AI1)
•
Start, pulse (DI1)
•
Stop, pulse (DI2)
•
Direction selection (DI3)
•
Constant speed/frequency selection (DI4, DI5)
Output signals
•
Analog output AO1: Output frequency
•
Analog output AO2: Motor current
•
Relay output 1: Ready run
•
Relay output 2: Running
•
Relay output 3: Fault (-1)
DI4 DI5
Operation/Parameter
Scalar control (default)
Vector control
0
0
Set frequency through AI1
Set speed through AI1
1
0
0
1
1
1
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...