Parameters 353
Enables adaptive voltage limits.
Adaptive voltage limits can be used if, for example, an IGBT
supply unit is used to raise the DC voltage level. If the
communication between the inverter and IGBT supply unit is
active, the voltage limits are related to the DC voltage
reference from the IGBT supply unit. Otherwise the limits are
calculated based on the measured DC voltage at the end of
the pre-charging sequence.
This function is also useful if the AC supply voltage to the
drive is high, as the warning levels are raised accordingly.
Disable
Adaptive voltage limits disabled.
0
Enable
Adaptive voltage limits enabled.
1
AC supply voltage estimated by calculation. Estimation is
done every time the drive is powered up and is based on the
rise speed of voltage level of the DC bus while the drive
charges the DC bus.
0
0…65535 V
Voltage.
10 = 1 V
Specifies how the control board of the drive is powered.
Internal 24V
The drive control board is powered from the drive power unit
it is connected to.
0
External 24V
The drive control board is powered from an external power
supply.
1
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note:
The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
0b0000
0b0000…0b1111
Hardware options configuration word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Reserved
1
ABB Sine filter
1 = An ABB sine filter is connected to the output of the drive.
2…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...