Parameters 179
Plug ‘n’ play configuration. Drive automatically detects and
enables any installed fieldbus or C-series option.
0x0000
0x0000...0xffff
Drive configuration 2.
1 = 1
10
Configuration of digital inputs and relay outputs.
Displays the electrical status of digital inputs DI1...DI6. The
activation/deactivation delays of the inputs (if
any are specified) are ignored.
Bits 0…5 reflect the status of DI1…DI6.
Example:
0000000000010011b = DI5, DI2 and DI1 are on,
DI3, DI4 and DI6 are off.
This parameter is read-only.
0b0000
0b0000...0b1111
Status for digital inputs.
1 = 1
Displays the status of digital inputs DI1…DI6. Bits 0…5 reflect
the delayed status of DI1…DI6.
Example:
0000000000010011b = DI5, DI2 and DI1 are on,
DI3, DI4 and DI6 are off.
This word is updated only after a 2 ms activation/deactivation
delay. When the value of a digital input changes, it must
remain the same in two consecutive samples, that is for 2 ms,
for the new value to be accepted.
This parameter is read-only.
0b0000
0b0000...0b1111
Delayed status for digital inputs.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Bit
Name
0
FLON-01
4
CMOD-02
1
FDNA-01
5
CPTC-02
2
FCNA-01
6
CHDI-01
3
CMOD-01
7...15
Reserved
Bit
Name
Description
0
DI1
1 = Digital input 1 is ON.
1
DI2
1 = Digital input 2 is ON.
2
DI3
1 = Digital input 3 is ON.
3
DI4
1 = Digital input 4 is ON.
4
DI5
1 = Digital input 5 is ON.
5
DI6
1 = Digital input 6 is ON.
6…15
Reserved
Bit
Name
Description
0
DI1
1 = Digital input 1 is ON.
1
DI2
1 = Digital input 2 is ON.
2
DI3
1 = Digital input 3 is ON.
3
DI4
1 = Digital input 4 is ON.
4
DI5
1 = Digital input 5 is ON.
5
DI6
1 = Digital input 6 is ON.
6…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...