192 Parameters
mA
Milliamperes.
10
Defines the filter time constant for analog input AI2. See
parameter
0.100 s
0.000…30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
4.000 mA
0.000…22.000
Minimum value of AI2.
1000 = 1 unit
Defines the maximum site value for analog input AI2.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
20.000 mA
0.000…22.000 mA
Maximum value of AI2.
1000 = 1 unit
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
.
(Changing the polarity settings of
can
effectively invert the analog input.)
0.000
-32768.000…
32767.000
Real value corresponding to minimum AI2 value.
1 = 1
Defines the real value that corresponds to the minimum
analog input AI2 value defined by parameter
.
See the drawing at parameter of
50.000
-32768.000…
32767.000
Real value corresponding to maximum AI2 value.
1 = 1
Value of analog input AI1 in percent of AI1 scaling (
-
).
0
0.00…100.00%
AI1 value
100 = 1%
Value of analog input AI2 in percent of AI2 scaling (
-
).
0
0.00…100.00%
AI2 value
100 = 1%
No.
Name/Value
Description
Def/FbEq16
AI
in
AI
scaled
)
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...