306
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
Make sure that you also set jumper S5 on the control circuit terminal block when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
■
H4-08: Terminal AM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-08
(0424)
Terminal AM Signal Level
Select
Sets the MFAO terminal AM output signal level.
0
(0, 2)
Note:
Make sure that you also set jumper S5 on the control circuit terminal block when you change this parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
■
H4-20: Analog Power Monitor 100% Level
No.
(Hex.)
Name
Description
Default
(Range)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when you set
U1-08 [Output Power]
for analog output.
0.00 kW
(0.00 - 650.00 kW)
Note:
•
When
H4-20 = 0.00 kW
, the output power monitor 10 V level = motor rated power.
◆
H5: Memobus/Modbus Communication
H5 parameters
configure the bypass to use MEMOBUS/Modbus communications.
You can use the MEMOBUS/Modbus protocol over the RS-485 port (terminals D+ and D-) in the bypass to use serial
communication with programmable controllers (PLC).
■
H5-01: Drive Node Address
No.
(Hex.)
Name
Description
Default
(Range)
H5-01
(0425)
Drive Node Address
Sets the communication slave address for drives.
1FH
(Determined by protocol)
Note:
•
Setting range differs by protocol:
–
BACnet: 0 to 7F
–
P1: 0 to FF
–
N2: 0 to FF
–
Modbus: 0 to FF
•
Restart the drive after you change the parameter setting.
•
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
To enable the drive to communicate with the controller (master) over MEMOBUS/Modbus communications, you
must set the drive with a slave address. Set
H5-01 ≠ 0
.
Set a slave address that is different from other slave devices.
■
H5-02: Communication Speed Selection
No.
(Hex.)
Name
Description
Default
(Range)
H5-02
(0426)
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
3
(Determined by protocol)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...