YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
399
The keypad will show an
[Emergency Override Test Pending]
message.
2. Activate an MFDI terminal set for
H1-xx = AF or B0 [Emergency Override FWD or Emergency Override REV]
.
The drive will start the Test Mode operation. The keypad will show an
[Emergency Override Test Mode]
message.
When the Emergency Override MFDI deactivates and the drive fully stops, Test Mode deactivates. Parameter
S6-07
then automatically returns to setting
0 [Fault Suppression]
.
Note:
•
The drive will keep the
S6-07
setting during a power-loss condition.
•
Parameter
o1-82 [Message Screen Display]
sets how the drive will show the messages on the keypad. Refer to
for more information.
■
S6-01: Emergency Override Speed
No.
(Hex.)
Name
Description
Default
(Range)
S6-01
(3236)
Emergency Override Speed
Sets the speed command for emergency override mode when
S6-02 = 0 [Emergency Override Ref
Selection = Use S6-01 Reference]
.
1.50 Hz
(1.50 - 60.00 Hz)
■
S6-02: Emergency Override Ref Selection
No.
(Hex.)
Name
Description
Default
(Range)
S6-02
(3237)
Emergency Override Ref
Selection
Sets the Emergency Override Speed Source:
0
(0 - 3)
0 : Use S6-01 Reference
1 : Use Frequency Reference
2 : System PID Mode
3 : Independent PID Mode
■
S6-03: EMOVR Independent PID Scale
No.
(Hex.)
Name
Description
Default
(Range)
S6-03
(323A)
EMOVR Independent PID
Scale
Sets the scaling on the Emergency PID Feedback and Setpoint (if programmed) Analog Inputs.
100.00
(0.10 - 600.00)
Note:
•
S6-05 [EMOVR Independent PID Unit Digit]
sets the resolution for this parameter.
•
S6-04 [EMOVR Independent PID Unit]
sets the units for this parameter.
■
S6-04: EMOVR Independent PID Unit
No.
(Hex.)
Name
Description
Default
(Range)
S6-04
(323B)
EMOVR Independent PID
Unit
Sets the units displayed for
S6-06 [EMOVR PID Setpoint]
when
S6-02 = 3 [Emergency Override Ref
Selection = Independent PID Mode]
.
48
(0 - 50)
0 : “WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 :
°
F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...