YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
711
Object ID
Object Name
(
Network Display, if
Different
)
Modbus Reg.
Active Text
Inactive Text
PV Access
BV86
Bypass Emergency Run
Drive Fwd Status
(
BYP Smk Prg DRV Stat
)
8784h: Bit 6
ON
OFF
R
BV87
Bypass Safety Status
(
BYP Safety Status
)
8784h: Bit 7
ON
OFF
R
BV88
Bypass BAS Interlock Status
(
BYP BAS Interlk Stat
)
8785h: Bit 0
ON
OFF
R
BV89
Bypass Run Status
(
BYP RUN Status
)
8785h: Bit 1
ON
OFF
R
BV90
Bypass Fault Status
(
BYP Fault Status
)
8785h: Bit 2
ON
OFF
R
BV91
Bypass Auto Transfer Status
(
BYP Auto Xfer Status
)
8785h: Bit 3
ON
OFF
R
BV92
Bypass Remote Transfer
Status
(
BYP Remote Xfer Stat
)
8785h: Bit 4
ON
OFF
R
BV93
Bypass Energy Savings
Status
(
BYP Energy Save Stat
)
8785h: Bit 5
ON
OFF
R
BV94
Bypass Motor 1 Select
Status
(
BYP Motor 1 Sel Stat
)
8785h: Bit 6
ON
OFF
R
BV95
Bypass Motor 2 Select
Status
(
BYP Motor 2 Sel Stat
)
8785h: Bit 7
ON
OFF
R
BV96
Bypass Drive Fault Status
(
BYP Drive Flt Status
)
8786h: Bit 0
ON
OFF
R
BV97
Bypass Safety Fault Status
(
BYP Safety Flt Stat
)
8786h: Bit 1
ON
OFF
R
BV98
Bypass BAS Interlock Fault
Status
(
BYP BAS ILock Status
)
8786h: Bit 2
ON
OFF
R
BV99
Bypass External Fault Status
(
BYP Ext Fault Stat
8786h: Bit 3
ON
OFF
R
BV100
Not Used BV100
-
-
-
R
BV101
Bypass Motor OL Status
(
BYP Motor OL Stat
)
8786h: Bit 5
ON
OFF
R
BV102
Bypass Motor 1 OL Status
(
BYP Motor 1 OL Stat
)
8786h: Bit 6
ON
OFF
R
BV103
Bypass Motor 2 OL Status
(
BYP Mtr 2 OL Stat
)
8786h: Bit 7
ON
OFF
R
BV104
Bypass Input Phase Loss
Status
(
BYP Input Phase Loss
)
8787h: Bit 0
ON
OFF
R
BV105
Bypass Drive Comms Status
(
BYP Drive Comms
)
8787h: Bit 2
ON
OFF
R
BV106
Bypass Loss of Load Status
(
BYP Loss Of Load
)
8787h: Bit 5
ON
OFF
R
BV107
Option Board on Drive
Status
(
BYP Option Brd Comms
)
8787h: Bit 4
ON
OFF
R
■
Device Object
The Device Object is the BACnet device to the network in this manual. The Device Object Instance ID, the Device
Object Name, and the Device Object Location are configurable. Refer to
for more information.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...