334
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
H3-xx = B: PID Feedback
L5-04: Interval Method Restart Time
Y1-08: Low Feedback Level
Y1-09: Low Feedback Lvl Fault Dly Time
Y1-14: Feedback Hysteresis Level
LFB Fault: Low Feedback Sensed
Figure 5.80 Auto Restart for Low Feedback Detection when b5-09 = 1
■
L5-41: Hi Feedback Flt Retry Selection
No.
(Hex.)
Name
Description
Default
(Range)
L5-41
(3671)
Hi Feedback Flt Retry
Selection
Sets the drive to do an Auto Restart when the drive detects an
HFB [High Feedback Sensed]
fault.
0
(0, 1)
0 : No Retry
1 : Retry
•
When
L5-41 = 1
and
b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)]
, the auto-restart
timer will not start timing until after the feedback level decreases to less than
Y1-11 [High Feedback Level]
(-
Y1-14
[High Feedback Hysteresis Level]
).
•
The drive will set the output frequency to zero during the auto-restart interval time.
•
If you remove the Run (or HAND) Command during the auto-restart interval time, the drive will immediately detect
and reset the fault.
•
When
L5-49 = 1 [Fault Retry Speed Search Select = Enabled]
, the drive will do a speed search when it resets and
restarts after a fault.
•
When you enable Thrust or Pre-Charge Modes, the drive will operate them correctly.
When
L5-41 = 1
, the drive operation will change when
b5-09 [PID Output Level Selection]
changes:
H3-xx = B: PID Feedback
L5-04: Interval Method Restart Time
Y1-11: High Feedback Level
Y1-12: High Feedback Lvl Fault Dly Time
Y1-14: Feedback Hysteresis Level
HFB Fault: High Feedback Sensed
Figure 5.81 Auto Restart for High Feedback Detection when b5-09 = 0 [Normal Output (Direct Acting)]
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...