82
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 3.2 Output and Control Wiring
Model
H6BP
Motor Wiring
Standard Motor Terminal
Block TB1
Ground Wiring
Control Wiring
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
D002
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D003
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D004
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D007
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D010
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D016
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D024
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D030
14-2
32
14-10, 8, 6-4,
or 2
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D046
14-2
32
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D059
14-2
32
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
D074
6-2/0
120
14-10, 8, 6-4,
or 2-1/0
35, 40, 45, or
50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
*1
24-16 is acceptable for solid wire or ferrule use only.
■
480 V Narrow Wire Gauges and Torques
Table 3.3 Input Wiring
Model
H6BP
Standard Non-Fused
Input Disconnect Switch S1
With Option PM
Circuit Breaker CB1
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
B001
20
14-8
20
15
(14-10) or (8-3/0)
50 or 120
B002
20
14-8
20
15
(14-10) or (8-3/0)
50 or 120
B003
20
14-8
20
15
(14-10) or (8-3/0)
50 or 120
B004
20
14-8
20
15
(14-10) or (8-3/0)
50 or 120
B007
20
14-8
20
20
(14-10) or (8-3/0)
50 or 120
B011
20
14-8
20
25
(14-10) or (8-3/0)
50 or 120
B014
20
14-8
20
35
(14-10) or (8-3/0)
50 or 120
B021
45
10, 8 or (6-2)
35, 40, or 50
50
(14-10) or (8-3/0)
50 or 120
B027
45
10, 8 or (6-2)
35, 40, or 50
60
(14-10) or (8-3/0)
50 or 120
B034
63
10, 8 or (6-2)
35, 40, or 50
70
(14-10) or (8-3/0)
50 or 120
B040
63
10, 8 or (6-2)
35, 40, or 50
80
(14-10) or (8-3/0)
50 or 120
B052
100
8-2/0
200
110
(14-10) or (8-3/0)
50 or 120
B065
100
8-2/0
200
150
(14-10) or (8-3/0)
50 or 120
B077
150
8-3/0
120
150
(14-10) or (8-3/0)
50 or 120
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...