258
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
•
The following setting values are available when using the PROFINET communication option card (SI-EP3).
–
0: Static
–
2: DCP
•
When
F7-13 = 0
, set parameters
F7-01 to F7-12 [IP Address 1 to Gateway Address 4]
to set the IP Address. Be sure to set a different IP
address for each drive on the network.
■
F7-14: Duplex Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
F7-14
(03F2)
Duplex Mode Selection
Sets the duplex mode setting method.
1
(0 - 8)
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
Port 1 is set to
“
Half
”
and port 2 is set to
“
Auto
”
.
4 : Half/Full
Port 1 is set to
“
Half
”
and port 2 is set to
“
Full
”
.
5 : Auto/Half
Port 1 is set to
“
Auto
”
and port 2 is set to
“
Half
”
.
6 : Auto/Full
Port 1 is set to
“
Auto
”
and port 2 is set to
“
Full
”
.
7 : Full/Half
Port 1 is set to
“
Full
”
and port 2 is set to
“
Half
”
.
8 : Full/Auto
Port 1 is set to
“
Full
”
and port 2 is set to
“
Auto
”
.
■
F7-15: Communication Speed Selection
No.
(Hex.)
Name
Description
Default
(Range)
F7-15
(03F3)
Communication Speed
Selection
Sets the communications speed.
10
(10, 100 - 102)
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Note:
Set this parameter when
F7-14 = 0
or
2 [Duplex Mode Selection = Half/Half or Full/Full]
.
■
F7-16: Timeout Value
No.
(Hex.)
Name
Description
Default
(Range)
F7-16
(03F4)
Timeout Value
Sets the detection time for a communications timeout.
0.0 s
(0.0 - 30.0 s)
Note:
Set this parameter to 0.0 to disable the connection timeout function.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...