3.5 Bypass PCB Control Circuit
94
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
◆
Bypass Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 3.12 Bypass Control Circuit Wire Gauges and Tightening Torques
Bypass Terminal
Block
Terminal
Tightening Torque
in
∙
lb
Recommended Gauge
AWG
Applicable Gauge
AWG
TB1
DO-7 - DO-10
4
18
26-14
TB2
DI-1 - DI-8, IG24, SHIELD
TB3
SHEILD, TXRX-, TXRX+, IG5
TB4
+10 Vdc, AI-1, COMMON
TB6
GROUND, GROUND
◆
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to
for the recommended external
dimensions and model numbers of the crimp ferrules.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Figure 3.10 External Dimensions of Crimp Ferrules
Table 3.13 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model
L (mm)
L1 (mm)
φ
d1 (mm)
φ
d2 (mm)
0.25 (24)
AI 0.25-8YE
12.5
8
0.8
2.0
0.34 (22)
AI 0.34-8TQ
12.5
8
0.8
2.0
0.5 (20)
AI 0.5-8WH
AI 0.5-8OG
14
8
1.1
2.5
0.75 (18)
AI 0.75-8 GY
14
8
1.3
2.8
◆
Bypass Control Circuit Terminal Block Input Functions
WARNING!
Sudden Movement Hazard. Correctly wire and test all control circuits to make sure that the control circuits operate
correctly. If you use a drive that has incorrect control circuit wiring or operation, it can cause death or serious injury.
WARNING!
Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06
≠
0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
NOTICE:
Damage to Equipment. Do not energize and de-energize the bypass more frequently than one time each 30 minutes. If
you frequently energize and de-energize the bypass, it can cause failure.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...