5.10 o: Keypad-Related Settings
368
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
o4-09: IGBT Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-09
(0525)
IGBT Maintenance Setting
Sets the
U4-07 [IGBT Maintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-09 = 0
to reset
U4-07
. When the
o4-09
setting changes, the count of
U4-07
starts
again as specified by the setting of
o4-09
. After you complete the configuration,
o4-09
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
■
o4-11: Fault Trace/History Init (U2/U3)
No.
(Hex.)
Name
Description
Default
(Range)
o4-11
(0510)
Fault Trace/History Init (U2/
U3)
Resets the records of Monitors
U2-xx [Fault Trace]
and
U3-xx [Fault History]
.
0
(0, 1)
Note:
When you initialize the drive with
A1-03 [Initialize Parameters]
, the drive will not reset the records for
U2-xx
and
U3-xx
.
0 : Disabled
Keeps the records of Monitors
U2-xx
and
U3-xx
.
1 : Enabled
Resets the records for Monitors
U2-xx
and
U3-xx
. After the reset, the drive automatically resets
o4-11
to
0
.
■
o4-12: kWh Monitor Initialization
No.
(Hex.)
Name
Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for
U4-10 [kWh, Lower 4 Digits]
and
U4-11 [kWh, Upper 5 Digits]
.
0
(0, 1)
Note:
When you initialize the drive with
A1-03 [Initialize Parameters]
, the drive will not reset
U4-10
and
U4-11
.
0 : No Reset
Keeps the monitor values for
U4-10
and
U4-11
.
1 : Reset
Resets the values of
U4-10
and
U4-11
. After the reset, the drive automatically resets
o4-12
to
0
.
■
o4-13: RUN Command Counter @ Initialize
No.
(Hex.)
Name
Description
Default
(Range)
o4-13
(0528)
RUN Command Counter @
Initialize
Resets the monitor values for
U4-02 [Num of Run Commands]
,
U4-24 [Number of Runs (Low)]
, and
U4-25 [Number of Runs (High)]
.
0
(0, 1)
0 : No Reset
Keeps the monitor values for
U4-02
,
U4-24, and U4-25
.
1 : Reset
Resets the values of
U4-02
,
U4-24
, and
U4-25
. After the reset, the drive automatically resets
o4-13
to
0
.
■
o4-22: Time Format
No.
(Hex.)
Name
Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available on an HOA keypad.
1
(0 - 2)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...