5.1 A: Initialization Parameters
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
175
shows which keypad screens are available for each
A1-01
settings.
Table 5.1 Access Level and Available Keypad Screens
Mode
Keypad Screen
A1-01 Setting
0
1
2
3
4
Drive Mode
Monitors
Yes
Yes
Yes
Yes
Yes
Programming Mode
Parameters
Yes
Yes
Yes
Yes
Yes
User Custom Parameters
No
Yes
Yes
Yes
No
Parameter Backup/
Restore
No
No
Yes
Yes
No
Modified Parameters/
Fault Log
No
No
Yes
Yes
Yes
Auto-Tuning
No
No
Yes
Yes
No
Initial Setup Screen
No
No
Yes
Yes
No
Diagnostic Tools
No
No
Yes
Yes
No
Note:
•
When you use
A1-04
and
A1-05 [Password Setting]
to set a password, you cannot change these parameters:
–
A1-01
–
A1-03 [Initialize Parameters]
–
A1-06 [Application Preset]
–
A2-01 to A2-32
•
When
H1-xx = 1B [MFDI Function Selection = Program Lockout]
, you must activate the terminal to change parameter settings.
•
When you use serial communications, you must send the Enter command from the controller to the drive and complete the serial
communication write process before you can use the keypad to change parameter settings.
■
A1-03: Initialize Parameters
No.
(Hex.)
Name
Description
Default
(Range)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0
(0, 1110, 2220)
Note:
•
After you initialize the drive, the drive automatically sets
A1-03 = 0
.
•
User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
0 : No Initialization
1110 : User Initialization
Sets parameters to the values set by the user as user settings. Set
o2-03 = 1 [User Parameter Default Value = Set
defaults]
to save the user settings.
You can save the adjusted parameter settings from the test run as user-set default values to the drive. When you make
changes to the parameter values after you save the settings as User Parameter Settings, initialize with
A1-03 = 1110
for the drive to set the parameters to the User Parameter Setting value.
Follow this procedure to save User Parameter setting values and to do a User Initialization:
1. Set parameters correctly for the application.
2. Set
o2-03 = 1 [User Parameter Default Value = Set defaults]
.
This saves parameter settings for a User Initialization.
The drive will automatically set
o2-03 = 0
.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...