8.4 Replace Drive Cooling Fans and Circulation Fans
564
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
5.
Push the tab on the back side of the fan finger guard and click it into place on the drive.
Figure 8.8 Install the Fan Finger Guard
6.
Energize the drive and set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
to reset the cooling fan operation
time.
■
Remove a Circulation Fan
Note:
Use this procedure only when you use one of these drive models:
•
2024CVx, 2031CVx
•
4021CVx to 4034CVx
Remove the drive cover before you start this procedure.
CAUTION!
Crush Hazard. Loosen the cover screws. Do not fully remove them. If you fully remove the cover screws, the terminal
cover can fall and cause moderate injury.
1.
Disconnect the connector and remove the cable from the hook.
A - Circulation fan
B - Hook
C - Fan cable
Figure 8.9 Disconnect the Connector and Remove the Cable
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...